Delta Electronics VFD-F Series manual AC Output Reactor Recommended Value, B-11

Models: VFD-F Series

1 161
Download 161 pages 45.18 Kb
Page 146
Image 146
AC Output Reactor Recommended Value

 

 

 

 

 

 

VFD-F Series

AC Output Reactor Recommended Value

 

 

 

230V, 50/60Hz, 3-Phase

 

 

 

 

 

kW

HP

Fundamental

Max. continuous

Inductance (mH)

 

Amps

Amps

3% impedance

5% impedance

 

 

 

 

0.75

1

8

12

3

5

 

 

1.5

2

8

12

1.5

3

 

 

2.2

3

12

18

1.25

2.5

 

 

3.7

5

18

27

0.8

1.5

 

 

5.5

7.5

25

37.5

0.5

1.2

 

 

7.5

10

35

52.5

0.4

0.8

 

 

11

15

55

82.5

0.25

0.5

 

 

15

20

80

120

0.2

0.4

 

 

18.5

25

80

120

0.2

0.4

 

 

22

30

100

150

0.15

0.3

 

 

30

40

130

195

0.1

0.2

 

 

37

50

160

240

0.075

0.15

 

460V, 50/60Hz, 3-Phase

 

 

 

 

 

kW

HP

Fundamental

Max. continuous

Inductance (mH)

 

 

Amps

Amps

3% impedance

5% impedance

 

 

 

 

 

 

0.75

1

4

6

9

12

 

 

1.5

2

4

6

6.5

9

 

 

2.2

3

8

12

5

7.5

 

 

3.7

5

12

18

2.5

4.2

 

 

5.5

7.5

18

27

1.5

2.5

 

 

7.5

10

18

27

1.5

2.5

 

 

11

15

25

37.5

1.2

2

 

 

15

20

35

52.5

0.8

1.2

 

 

18.5

25

45

67.5

0.7

1.2

 

 

22

30

45

67.5

0.7

1.2

 

 

30

40

80

120

0.4

0.7

 

 

37

50

80

120

0.4

0.7

 

 

45

60

100

150

0.3

0.45

 

 

55

75

130

195

0.2

0.3

 

 

75

100

160

240

0.15

0.23

 

 

90

125

160

240

0.15

0.23

 

 

110

150

200

300

0.11

0.185

 

 

185

250

320

480

0.75

0.125

 

 

220

300

400

600

0.06

0.105

 

B

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

B-11