5.11 Group 10: PID Control Parameters

10 - 00 Input Terminal for PID Feedback

Settings

00: No function

 

01: Input via AVI

 

02: Input via ACI1

 

03: Input via ACI2

 

04: Input via External Reference

This parameter is to set the source of PID control feedback signal. The source could be AVI, ACI1, ACI2 or external reference that defined by 04-24.

When this parameter is set to 00, PID feedback control function is disabled.

When this parameter is set to 02/03 and analog input current of ACI1/ACI2 is lower than Pr.04-13/Pr.04-17, EF warning will pup-up.

If this parameter isn’t set to 00, AC drive will automatically start-up PID feedback control. Output frequency is calculated by master frequency and PID feedback signal.

 

+

 

 

 

 

 

Difference

 

 

 

 

 

 

 

 

Target

 

 

 

 

Position/

Range

P

 

 

I

 

Upper

+

 

 

 

 

 

 

 

 

value

 

 

 

 

 

 

 

Negative

 

 

 

 

Bound for

 

 

 

02-00

 

 

 

 

 

 

 

Feedback

 

10-03

10-04

 

Integral

+

 

 

 

 

 

 

 

 

 

10-02

 

 

 

 

 

 

Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

10-06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Detection

 

 

 

10-05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal

 

 

 

 

 

 

 

 

 

 

 

 

10-01

 

 

 

 

 

 

 

 

 

 

 

 

+

10 - 01

PID Control Detection Signal Reference

Factory Setting: 1000.0

 

Settings

0.0-6550.0

Unit: 0.1

Please refer to 04-09 to 04-20 if this parameter is set to PID feedback control.

 

 

 

10 - 02

PID Feedback Control Method

Factory Setting: 00

 

Settings

00: Negative feedback control

 

 

 

01: Positive feedback control

 

This parameter could set the calculation method of deviation signal during PID feedback control circuit.

When this parameter is set to 00: when negative feedback control, the deviation equation is deviation = target value – detection signal. When increasing output frequency will increase detection value, this setting should be chose.