Delta Electronics VFD-F Series manual 02-07

Models: VFD-F Series

1 161
Download 161 pages 45.18 Kb
Page 118
Image 118
02-07

 

 

 

 

 

VFD-F Series

 

 

 

 

 

 

 

Parameters

Functions

Settings

Factory

Customer

 

 

 

 

Setting

 

 

02-07

Loss of ACI Signal

00: Decelerate to 0Hz

01

 

 

 

 

01: E.F.

 

 

 

 

 

02: Continue operation by the

 

 

 

 

 

last frequency command

 

 

 

02-08

Start-up Display Selection

Bit0~1: 00 = F LED

00

 

 

 

 

01 = H LED

 

 

 

 

 

10 = U LED (special

 

 

 

 

 

display)

 

 

 

 

 

11 = Fwd / Rev

 

 

 

 

 

Bit2: 0 = Fwd LED /

 

 

 

 

 

1 = Rev LED

 

 

 

 

 

Bit3~5: 000 = 1st 7-step

 

 

 

 

 

001 = 2nd 7-step

 

 

 

 

 

010 = 3rd 7-step

 

 

 

 

 

011 = 4th 7-step

 

 

 

 

 

100 = 5th 7-step

 

 

 

 

 

Bit6~7: Reserved

 

 

 

02-09

Special Display

00: A displays output current of

00

 

 

 

 

AC drive

 

 

 

 

 

01: U displays DC-Bus voltage

 

 

 

 

 

of AC drive

 

 

 

 

 

02: E displays RMS of output

 

 

 

 

 

voltage

 

 

 

 

 

03: P displays feedback Signal

 

 

 

 

 

04: PLC display auto procedure

 

 

 

 

 

state

 

 

 

02-10

User Defined Coefficient

0.01~160.00

1.00

 

 

 

 

 

 

 

 

02-11

Flying Start

00: Disable

00

 

 

 

 

01: Enable (Dc brake disabled)

 

 

 

02-12

Flying Start Frequency

00: Trace from master

00

 

 

 

 

frequency command

 

 

 

 

 

01: Trace from maximum

 

 

 

 

 

setting frequency 01-00

 

 

 

02-13

Master Frequency Memory

00: Do not remember the last

01

 

 

 

Setting

known frequency

 

 

 

 

 

01: Remember the last known

 

 

 

 

 

frequency

 

 

8

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

8-5