Delta Electronics VFD-F Series manual B.2 AMD-EMI Filter Cross Reference

Models: VFD-F Series

1 161
Download 161 pages 45.18 Kb
Page 143
Image 143
B.2 AMD-EMI Filter Cross Reference

Manual background VFD-F Series

B.2 AMD-EMI Filter Cross Reference

AC Drives

VFD007F23A/H, VFD015F23A/H, VFD022F23A/H, VFD037F23A/H

VFD110F23A/H, VFD055F23A/H, VFD075F23A/H, VFD185F43A/H

VFD150F23A/H, VFD220F43A/H, VFD300F43A/H, VFD370F43A/H

VFD220F23A/H, VFD185F23A/H, VFD300F23A/H, VFD450F43A/H

VFD370F23A/H, VFD550F43A/H

VFD750F43A/H

Installation

EMI Model Number

26TDT1W4C

50TDS4W4C

100TDS84C

150TDS84C

180TDS84C

200TDDS84C

All electrical equipment, including AC motor drives, will generate high-frequency/low-frequency noise and will interfere with peripheral equipment by radiation or conduction when in operation. By using an EMI filter with correct installation, much interference can be eliminated. It is recommended to use DELTA EMI filter to have the best interference elimination performance.

We assure that it can comply with following rules when AC motor drive and EMI filter are installed and wired according to user manual:

„EN61000-6-4

„EN61800-3: 1996 + A11: 2000

„EN55011 (1991) Class A Group 1 (1st Environment, restricted distribution)

General precaution

1.EMI filter and AC motor drive should be installed on the same metal plate.

2.Please install AC motor drive on footprint EMI filter or install EMI filter as close as possible to the AC motor drive.

3.Please wire as short as possible.

4.Metal plate should be grounded.

5.The cover of EMI filter and AC motor drive or grounding should be fixed on the metal plate and the contact area should be as large as possible.

Choose suitable motor cable and precautions

Improper installation and choice of motor cable will affect the performance of EMI filter. Be sure to observe the following precautions when selecting motor cable.

1.Use the cable with shielding (double shielding is the best).

2.The shielding on both ends of the motor cable should be grounded with the minimum length and maximum contact area.

3.Remove any paint on metal saddle for good ground contact with the plate and shielding.

B-8