zCommand code: 08H, loop detection

This command is used to test the communication condition between master control equipment (usually is PC or PLC) and AC drive. AC drive will deliver the data that received from AC drive to master control equipment.

For example:

ASCII mode:

Command message:

STX

‘:’

ADR 1

‘0’

ADR 0

‘1’

CMD 1

‘0’

CMD 0

‘8’

data

‘0’

Starting

‘0’

address

‘0’

data

‘0’

‘1’

 

‘7’

 

‘7’

LRC CHK 1

‘0’

‘7’

LRC CHK 0

‘0’

END 1

CR

END 0

LF

RTU mode:

Response message:

STX

‘:’

ADR 1

‘0’

ADR 0

‘1’

CMD 1

‘0’

CMD 0

‘8’

data

‘0’

Starting

‘0’

 

‘0’

 

‘0’

data

‘1’

 

‘7’

 

‘7’

 

‘0’

LRC CHK 1

‘7’

LRC CHK 0

‘0’

END 1

CR

END 0

LF

Error response message

STX

‘:’

ADR 1

‘0’

ADR 0

‘1’

CMD 1

‘8’

CMD 0

‘8’

Error

‘0’

code

‘2’

LRC CHK 0

‘6’

LRC CHK 1

‘D’

END 1

CR

END 0

LF

Command message:

ADR

01H

CMD

08H

data

00H

Starting address

00H

data

17H

 

70H

CRC CHK LOW

EEH

CRC CHK HIGH

1FH

Response message:

ADR

01H

CMD 1

08H

data

00H

Starting address

00H

data

17H

 

70H

CRC CHK LOW

EEH

CRC CHK HIGH

1FH

Error response message

ADR

01H

CMD 1

88H

Error code

02

CRC CHK LOW

E0H

CRC CHK HIGH

6DH

zCommand code: 10H, write continuous words

For example, modify multi-step speed setting of AC drive (address 01H) 05-00=50.00(1388H)05-01=40.00(0FA0H)