Fault

Fault Descriptions

Corrective Actions

Name

 

 

 

Ground fault:

 

 

The AC drive output is

 

 

abnormal. When the

 

 

output terminal is

 

 

grounded (short circuit

Ground fault:

 

current is 50% more

1. Check whether the IGBT power module

 

than the AC drive rated

 

current), the AC drive

is damaged.

 

2. Check for possible poor insulation at the

 

power module may be

 

output line.

 

damaged. The short

 

 

 

circuit protection is

 

 

provided for AC drive

 

 

protection, not user

 

 

protection.

 

 

External Base Block.

1. When the external input terminal (B.B) is

 

active, the AC drive output will be turned

 

AC drive output is turned

off.

 

off.

2. Disable this connection and the AC drive

 

 

will begin to work again.

 

 

1. Check parameter settings (Pr.10-00)

 

PID Feedback Signal

and AVI/ACI1/ACI2 wiring.

 

2. Check for possible fault between system

 

Error

 

reaction time and the feedback signal

 

 

 

 

detection time (Pr.10-08/Pr.10-09).

 

Fan Power Fault

Return to the factory.

 

(150~300HP)

 

 

 

 

Remove any foreign objects on the

 

Fan 1 fault (150~300HP)

heatsinks and check for possible dirty heat

 

 

sink fins.

 

Fan 2 fault (150~300HP)

Remove any foreign objects on the

 

heatsinks and check for possible dirty heat

 

 

sink fins.

 

Fan 3 fault (150~300HP)

Remove any foreign objects on the

 

heatsinks and check for possible dirty heat

 

 

sink fins.

 

 

 