ACI 1/2

VFD-F Series

Terminal Symbols

Terminal Functions

Factory Settings

+10V

Potentiometer power

+10V 20mA

source

 

 

AVI

Analog voltage Input

0 to +10V correspond to Max. operation

frequency

 

 

ACI 1/2

Analog current Input

4 to 20mA correspond to Max. operation

frequency

 

 

AFM 1

Analog frequency

0 to 10V correspond to Max. operation

/current meter 1

frequency

 

AFM 2

Analog frequency

4 to 20mA correspond to 2 times of output

/current meter 2

current

 

ACM

Analog control signal

 

(common)

 

 

 

* Control signal wiring size: 18 AWG (0.75 mm2).

Analog input terminals (ACI1, ACI2, ACM)

„Analog input signals are easily affected by external noise. Use shielded wiring and keep it as short as possible (<20m) with proper grounding. If the noise is inductive, connecting the shield to terminal ACM can bring improvement.

„If the analog input signals are affected by noise from the AC motor drive, please connect a capacitor and ferrite core as indicated in the following diagrams:

Analog input terminals (ACI1, ACI2, ACM) ACI1/ACI2

wind each wire 3 times or more around the core C

Digital inputs (FWD, REV, MI1~MI8, DCM) ACM

ferrite core

wind each wire 3 times or more around the core

Digital inputs (FWD, REV, MI1~MI8, DCM)

„When using contacts or switches to control the digital inputs, please use high quality components to avoid contact bounce.