5.10 Group 9: Communication Parameters

 

 

 

 

VFD-F Series

5.10 Group 9: Communication Parameters

 

 

 

 

Factory Setting: 01

09 - 00

Communication Address

 

 

 

 

 

 

 

Settings

01-254

 

 

 

 

00: Disable

 

If the AC drive is controlled by RS-485 serial communication, the communication address

for this drive must be set via this parameter.

09 - 01 Transmission Speed (Baud Rate)

Settings

00: Baud rate 4800

 

01: Baud rate 9600

 

02: Baud rate 19200

 

03: Baud rate 38400

Factory Setting: 01

This parameter determines transmission speed of AC drive communication.

09 - 02

Transmission Fault Treatment

 

 

Factory Setting: 03

 

 

 

 

 

 

 

Settings

00: Warn and keep operating

 

 

 

 

 

01: Warn and RAMP to stop

 

02: Warn and COAST to stop

03: No warning and no display

This parameter is set to detect if an error occurs and take actions.

09 - 03

Time-out Detection during Transmission

Factory Setting: 00

 

Settings

00: Disable

 

 

 

01: Enable

 

This parameter is used for ASCII mode. When this parameter is set to 01, indicates that the over time detection is enable, the time slot between each character can’t exceed 500 ms.

09 - 04

Communication Format

Factory Setting: 00

 

Settings

00: 7-bit for ASCII

 

 

 

01: 8-bit for ASCII

 

 

 

02: 8-bit for RTU

 

 

 

 

09 - 05

Even/Odd Parity and Stopping Parity Setting

Factory Setting: 00

 

Settings

00: None parity + 2 stop bit

 

 

 

01: Even parity + 2 stop bit

 

02: Odd parity + 2 stop bit

03: None parity + 1 stop bit

04: Even parity + 1 stop bit

05: Odd parity + 1 stop bit

This parameter determines the communication format of serial communication.