Delta Electronics VFD-F Series manual Setting 04 0-10V = 0.0 - output power factor

Models: VFD-F Series

1 161
Download 161 pages 45.18 Kb
Page 51
Image 51
Setting 04: 0-10V = 0.0 - output power factor 1.0
Factory Setting: 00

Manual background VFD-F Series

Setting 04: 0-10V = 0.0 - output power factor 1.0

When using 0-20mA output, please refer to Pr. 3-14.

Maximum impedance loading of analog output 2 (AFM2) can’t be greater than 500 ohms.

03 - 12 Analog Output Gain 1

03 - 13 Analog Output Gain 2

Settings 01~200%

This parameter is to determine analog output gain.

Factory Setting: 100

Factory Setting: 100

The analog output is limited to 10V and 20mA. The gain is designed to offer a normally small output signal to be enlarged for easier viewing on a meter.

03 - 14

Analog Output 2

Selection

Factory Setting: 01

 

Settings

00: 0~20mA

 

 

 

01: 4~20mA

 

This parameter selects the output range of Analog Output 2 (AFM2).

03 - 15 DC Fan Control

Settings

00: Fan runs on power up.

 

01: Fan begins upon a RUN command. Fan stops 1 minute after a

 

STOP command.

 

02: Fan begins upon a RUN command. Fan stops after a STOP

 

command

 

03: Fan is controlled by temperature. Approximately a 60°C

 

temperature will start the fan.

This parameter determines DC fan control method.