Delta Electronics VFD-F Series manual Group 2 Digital Output/Input Parameter

Models: VFD-F Series

1 161
Download 161 pages 45.18 Kb
Page 117
Image 117
Group 2 Digital Output/Input Parameter

Manual background VFD-F Series

Group 2 Digital Output/Input Parameter

 

Parameters

Functions

Settings

Factory

Customer

 

 

 

 

Setting

 

 

02-00

Source of Frequency

00: via keypad

00

 

 

 

Command

01: via analog input AVI

 

 

 

 

 

02: via analog input ACI1

 

 

 

 

 

03: via analog input ACI2

 

 

 

 

 

04: via RS485 serial

 

 

 

 

 

communication

 

 

 

 

 

05: via External Reference

 

 

 

02-01

Source of Operation

00: Controlled by the digital

00

 

 

 

Command

keypad

 

 

 

 

 

01: Controlled by the external

 

 

 

 

 

terminals, keypad STOP

 

 

 

 

 

enabled.

 

 

 

 

 

02: Controlled by external

 

 

 

 

 

terminals, keypad STOP

 

 

 

 

 

disabled.

 

 

 

 

 

03: Controlled by the RS-485

 

 

 

 

 

communication interface,

 

 

 

 

 

keypad STOP enabled.

 

 

 

 

 

04: Controlled by the RS-485

 

 

 

 

 

communication interface,

 

 

 

 

 

keypad STOP disabled.

 

 

 

02-02

Stop Method

00:Stop = ramp to stop, E.F.

00

 

 

 

 

(External Fault) = coast to

 

 

 

 

 

stop

 

 

 

 

 

01:Stop = coast to stop, E.F. =

 

 

 

 

 

coast to stop

 

 

 

 

 

02:Stop = ramp to stop, E.F. =

 

 

 

 

 

ramp to stop

 

 

 

 

 

03:Stop = coast to stop, E.F. =

 

 

 

 

 

ramp to stop

 

 

 

02-03

PWM Carrier Frequency

1~10HP: 4000~10000Hz

9000Hz

 

 

 

Selections

15~30HP: 3000~9000Hz

6000Hz

 

 

 

 

40HP: 2000~6000Hz

4000Hz

 

 

02-04

Forward/Reverse Enable

00: Forward enabled

00

 

 

 

 

01: Reverse disabled

 

 

 

 

 

02: Forward disabled

 

 

 

02-05

2-wire/3-wire Operation

00: 2-wire (#1), FWD/STOP,

00

 

 

 

Control Modes

REV/STOP

 

 

 

 

 

01: 2-wire (#2), RUN/STOP,

 

 

 

 

 

REV/FWD

 

 

 

 

 

02: 3-wire

 

 

 

02-06

Line Start Lockout

00: Disabled

01

 

 

 

 

01: Enabled

 

 

8-4

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

Page 117
Image 117
Delta Electronics VFD-F Series manual Group 2 Digital Output/Input Parameter