Fault

Fault Descriptions

Corrective Actions

Name

 

 

 

 

1. Ensure that the ambient temperature

 

 

falls within the specified temperature

 

 

range.

 

The AC drive

2. Make sure that the ventilation holes are

 

not obstructed.

 

temperature sensor

 

3. Remove any foreign objects on the

 

detects excessive heat.

 

heatsinks and check for possible dirty

 

 

 

 

heat sink fins.

 

 

4. Provide enough spacing for adequate

 

 

ventilation.

 

The AC drive detects

Check whether the input voltage falls within

 

that the DC bus voltage

 

has fallen below its

the rated AC drive’s input voltage.

 

minimum value.

 

 

The AC drive detects

 

 

excessive drive output

1. Check whether the motor is overloaded.

 

current.

 

Note: The AC drive can

2. Reduce torque compensation setting as

 

withstand up to 150% of

set in Pr.7-02.

 

the rated current for a

3. Increase the AC drive’s output capacity.

 

maximum of 60

 

 

seconds.

 

 

 

1. Check for possible motor overload.

 

 

2. Check electronic thermal overload

 

Internal electronic

setting.

 

3. Increase motor capacity.

 

overload trip

 

4. Reduce the current level so that the drive

 

 

 

 

output current does not exceed the value

 

 

set by the Motor Rated Current Pr.7-00.

 

Motor overload. Check

1. Reduce the motor load.

 

2. Adjust the over-torque detection setting

 

the parameter settings

 

to an appropriate setting (Pr.06-03 to

 

(Pr.6-03 to Pr.6-05)

 

Pr.06-05).

 

 

 

GFF hardware error

Return to the factory.

 

CC (Current Clamp)

Return to the factory.