| Chapter 6 Fault Code | |
Fault | Fault Descriptions |
| Corrective Actions |
|
Name |
|
| ||
|
|
|
| |
|
| 1. |
| |
|
|
| possible poor insulation at the output line. |
|
|
| 2. Sudden increase in motor loading: Check for |
| |
|
| possible motor stall. |
| |
| constant speed operation |
|
| |
| 3. AC motor drive output power is too small: |
| ||
|
|
| ||
|
|
| Replace the AC motor drive with the next |
|
|
|
| higher power model. |
|
|
|
|
| |
|
| 1. When |
| |
| External Fault |
| are set to external fault, the AC motor drive |
|
|
| stops output U, V and W. |
| |
|
| 2. Give RESET command after fault has been |
| |
|
|
| cleared. |
|
| Internal EEPROM can not be | Return to the factory. |
| |
| programmed. |
| ||
|
|
|
| |
| Internal EEPROM can not be | Return to the factory. |
| |
| programmed. |
| ||
|
|
|
| |
|
| 1. | Switch off power supply. |
|
| Drive’s internal circuitry | 2. | Check whether the input voltage falls within the |
|
| abnormal. |
| rated AC drive input voltage. Switch on the AC |
|
|
|
| drive. |
|
| OH error |
|
|
|
| OV error |
|
|
|
| LV error | Return to the factory. |
| |
| Current detection error |
| ||
| DC BUS detection error |
|
|
|
|
|
|
|
|
| Current detection error |
|
|
|
|
| When (one of) the output terminal(s) is grounded, |
| |
|
| short circuit current is more than 50% of AC motor |
| |
|
| drive rated current, the AC motor drive power |
| |
|
| module may be damaged. |
| |
|
| NOTE: The short circuit protection is provided |
| |
| Ground fault | for AC motor drive protection, not for |
| |
|
| protection of the user. |
| |
|
| 1. Check whether the IGBT power module is |
| |
|
|
| damaged. |
|
|
| 2. Check for possible poor insulation at the |
| |
|
|
| output line. |
|
|
| 1. | When the external input terminal (B.B) is |
|
| External Base Block. |
| active, the AC motor drive output will be |
|
|
| turned off. |
| |
| (Refer to Pr. |
|
| |
| 2. | Deactivate the external input terminal (B.B) to |
| |
|
|
| ||
|
|
| operate the AC motor drive again. |
|
|
| 1. Check if the motor is suitable for operation by |
| |
| Auto accel/decel failure |
| AC motor drive. |
|
| 2. | Check if the regenerative energy is too large. |
| |
|
|
| ||
|
| 3. | Load may have changed suddenly. |
|