| Chapter 5 | ||
Group 7: Motor Parameters |
|
|
| ||
|
|
|
|
| |
Motor Rated Current |
| Unit: 1 |
| ||
| Settings | d30 to d120% |
| Factory Setting: d85 | |
|
|
| |||
This parameter will limit the AC drive output current in order to prevent the motor from | |||||
overheating. |
|
|
|
| |
|
|
|
|
| |
Motor |
| Unit: 1 | |||
|
|
|
|
|
|
| Settings | d0 to d90% |
| Factory Setting: d50 | |
|
|
|
|
|
|
The rated current of the AC drive is regarded as 100%. Motor setting of
Torque Compensation | Unit: 0.1 | ||
| Settings | d0 to d10 | Factory Setting: d1 |
|
|
|
|
This parameter may be set so that the AC drive will increase its voltage output during
Slip Compensation | Unit: 0.01 | ||
| Settings | d0.0 to d10.0 | Factory Setting: d0.0 |
|
|
|
|
While driving an asynchronous motor, load on the AC drive will increase, causing an increase in slip. This parameter may be used to compensate the nominal slip within a range of 0 to 10. When the output current of the AC drive is greater than the motor
Revision August 2006, SE08, SW V2.61 |