Chapter 5 ParametersVFD-S Series

DC Braking during Start-up is used for loads that may move before AC drive starts, such as fans and pumps. These loads may also be moving in the wrong direction. Under such circumstances, DC Braking can be executed to hold the load in position before applying a forward motion.

DC Braking during stopping is used to decrease stopping time and also to hold a stopped load in position. For high inertial loads, a dynamic braking resistor may be needed for quick decelerations.

8-04Momentary Power Loss Operation Selection

 

 

 

 

 

Factory Setting: d0

 

Settings

d0

Operation stops after momentary power loss

 

 

 

d1

Operation continues after momentary power loss, speed search

 

 

 

starts with the Master Frequency reference value

 

 

d2

Operation continues after momentary power loss, speed search

 

 

 

starts with the minimum frequency

 

 

 

 

 

8-05

Maximum Allowable Power Loss Time

Unit: 0.1

 

Settings

d0.3 to d5.0Sec

Factory Setting: d2.0

 

 

 

 

 

 

During a power loss, if the power loss time is less than the time defined by this parameter, the AC drive will resume operation. If the Maximum Allowable Power Loss Time is exceeded, the AC drive output is then turned off.

8-06

Base Block Speed Search

Unit: 0.1

 

Settings

d0.3 to d5.0Sec

Factory Setting: d0.5

 

 

 

 

When a momentary power loss is detected, the AC drive turns off for a specified time interval determined by Pr.8-06 before resuming operation. This time interval is called Base-Block. This parameter should be set to a value where the residual output voltage is nearly zero, before the drive resumes operation.

This parameter also determines the searching time when performing external Base-Block and fault reset.

8-07

Current Limit for Speed Search

Unit: 1

 

Settings

d30 to d200

Factory Setting: d150

 

 

 

 

Revision August 2006, SE08, SW V2.61

5-59

Page 116
Image 116