Chapter 5 ParametersVFD-S Series
DC Braking during
DC Braking during stopping is used to decrease stopping time and also to hold a stopped load in position. For high inertial loads, a dynamic braking resistor may be needed for quick decelerations.
|
|
|
|
| Factory Setting: d0 |
| Settings | d0 | Operation stops after momentary power loss |
| |
|
| d1 | Operation continues after momentary power loss, speed search | ||
|
|
| starts with the Master Frequency reference value | ||
|
| d2 | Operation continues after momentary power loss, speed search | ||
|
|
| starts with the minimum frequency |
| |
|
|
|
| ||
Maximum Allowable Power Loss Time | Unit: 0.1 | ||||
| Settings | d0.3 to d5.0Sec | Factory Setting: d2.0 | ||
|
|
|
|
|
|
During a power loss, if the power loss time is less than the time defined by this parameter, the AC drive will resume operation. If the Maximum Allowable Power Loss Time is exceeded, the AC drive output is then turned off.
Base Block Speed Search | Unit: 0.1 | ||
| Settings | d0.3 to d5.0Sec | Factory Setting: d0.5 |
|
|
|
|
When a momentary power loss is detected, the AC drive turns off for a specified time interval determined by
This parameter also determines the searching time when performing external
Current Limit for Speed Search | Unit: 1 | ||
| Settings | d30 to d200% | Factory Setting: d150 |
|
|
|
|