Chapter 5 ParametersVFD-S Series

 

Group 8: Special Parameters

 

 

 

 

8-00

DC Braking Current Level

Unit: 1

 

Settings

d0 to d30%

Factory Setting: d0

 

 

 

 

This parameter determines the level of DC Braking Voltage Level output to the motor during start-up and stopping. When setting DC Braking Voltage, the Maximum Output Voltage (Pr.1-

02)is regarded as 100%. It is recommended to start with a low DC Braking Voltage Level and then increase until proper holding torque has been attained.

8-01

DC Braking Time during Start-up

Unit: 0.1

 

Settings

d0.0 to d60.0 sec

Factory Setting: d0.0

 

 

 

 

This parameter determines the duration of time that the DC Braking Current will be applied to the motor during the AC drive start-up.

8-02

DC Braking Time during Stopping

Unit: 0.1

 

Settings

d0.0 to d60.0 sec

Factory Setting: d0.0

 

 

 

 

This parameter determines the duration of time that the DC braking voltage will be applied to the motor during stopping. If stopping with DC Braking is desired, then Pr.2-02 must be set to RAMP stop (d0).

8-03

Start-Point for DC Braking

Unit: 0.1

 

Settings

d0.0 to d400Hz

Factory Setting: d0.0

 

 

 

 

This parameter determines the frequency when DC Braking will begin during deceleration.

Output Frequency

 

 

 

Start-Point for

 

 

 

 

 

DC Braking

 

 

01-05

 

 

Time during

 

 

 

 

Stopping

 

 

 

Minimum Output

 

 

 

 

Frequency

 

 

08-03

Time

 

 

 

 

 

 

 

 

Operation

08-01

 

 

 

08-02

 

Command

 

ON

 

OFF

 

 

 

 

 

DC Braking Voltage %

5-58

Revision August 2006, SE08, SW V2.61

Page 115
Image 115
Delta Electronics 460V Series, 230V Series, 115V Series manual Output Frequency, Group 8 Special Parameters