Appendix B AccessoriesVFD-S Series

Application 3

 

Question

Used to improve the input power factor, to

When the mains power capacity is too large,

reduce harmonics and provide protection from

line impedance will be small and the charge

AC line disturbances. (surges, switching

current will be too high. This may damage AC

spikes, short interruptions, etc.). The AC line

motor drive due to higher rectifier

reactor should be installed when the power

temperature.

supply capacity is 500kVA or more and

 

exceeds 6 times the inverter capacity, or the

 

mains wiring distance 10m.

 

 

Correct wiring

 

small-capacity

large-capacity

 

 

AC motor drive

power

reactor

 

motor

B-14