Chapter 2 Installation and Wiring
2.1 Ambient Conditions
Install the AC motor drive in an environment with the following conditions:
Operation | Air Temperature: | |
|
| |
|
| mounting |
| Relative Humidity: | <90%, no condensation allowed |
| Atmosphere pressure: | 86 ~ 106 kPa |
| Installation Site Altitude: | <1000m |
| Vibration: | <20Hz: 9.80 m/s2 (1G) max |
|
| 20 ~ 50Hz: 5.88 m/s2 (0.6G) max |
Storage | Temperature: | |
Transportation | Relative Humidity: | <90%, no condensation allowed |
| Atmosphere pressure: | 86 ~ 106 kPa |
| Vibration: | <20Hz: 9.80 m/s2 (1G) max |
|
| 20 ~ 50Hz: 5.88 m/s2 (0.6G) max |
Pollution Degree | 2: good for a factory type environment. |
CAUTION!
1.Operating, storing or transporting the AC motor drive outside these conditions may cause damage to the AC motor drive.
2.Failure to observe these precautions may void the warranty!
2.2 Installation
1.Mount the AC motor drive vertically on a flat vertical surface by using bolts or screws. Other directions are not allowed.
2.The AC motor drive will generate heat during operation. Allow sufficient space around the unit for heat dissipation.
3.The heat sink temperature may rise to 90°C when running. The material on which the AC motor drive is mounted must be noncombustible and be able to withstand this high temperature.
4.When the AC motor drive is installed in a confined space (e.g. cabinet), the surrounding temperature must be within 10 ~ 40°C with good ventilation. DO NOT install the AC motor drive in a space with bad ventilation.