Chapter 5 ParametersVFD-S Series

Group 6: Protection Parameters

6-00

Over-Voltage Stall Prevention

Unit: 0.1

 

 

 

Factory Setting: d1

 

Settings d0

Disable

 

 

d1

Enable

 

 

 

 

 

During deceleration, the motor DC bus voltage may exceed its Maximum Allowable Value due to motor regeneration. When this function is enabled, the AC drive will stop decelerating. Maintaining a constant output frequency when it happens. The AC drive will only resume deceleration when the voltage drops below preset value.

NOTE

With a moderate inertial load, the over-voltage during deceleration won’t happen, and the drive will stop in programmed time. The AC drive will automatically extend the deceleration time with high inertial loads. If deceleration time is critical for the application, then dynamic braking resistors should be used.

6-01

Over-Voltage Stall Prevention Level

Unit: 1

 

Settings 230V Series d350 to d410V

Factory Setting: 390

 

460V Series d700 to d820V

Factory Setting: 780

During deceleration, the DC bus voltage may exceed its maximum allowable value due to motor regeneration. When this function is enabled, the AC drive will stop decelerating. Maintaining a constant output frequency when it happens. The AC drive will resume deceleration when the voltage drops below preset value.

With a moderate inertial load, the over-voltage during deceleration won’t happen, and the drive will stop in programmed time. The AC drive will automatically extend the deceleration time with high inertial loads. If deceleration time is critical for the application, then dynamic braking resistors should be used.

5-52

Revision August 2006, SE08, SW V2.61

Page 109
Image 109
Delta Electronics 460V Series, 230V Series, 115V Series manual Group 6 Protection Parameters