Chapter 5 ParametersVFD-S Series
Group 6: Protection Parameters
Unit: 0.1 | |||
|
|
| Factory Setting: d1 |
| Settings d0 | Disable |
|
| d1 | Enable |
|
|
|
|
|
During deceleration, the motor DC bus voltage may exceed its Maximum Allowable Value due to motor regeneration. When this function is enabled, the AC drive will stop decelerating. Maintaining a constant output frequency when it happens. The AC drive will only resume deceleration when the voltage drops below preset value.
NOTE
With a moderate inertial load, the
Unit: 1 | ||
| Settings 230V Series d350 to d410V | Factory Setting: 390 |
| 460V Series d700 to d820V | Factory Setting: 780 |
During deceleration, the DC bus voltage may exceed its maximum allowable value due to motor regeneration. When this function is enabled, the AC drive will stop decelerating. Maintaining a constant output frequency when it happens. The AC drive will resume deceleration when the voltage drops below preset value.
With a moderate inertial load, the
Revision August 2006, SE08, SW V2.61 |