Chapter 5 ParametersVFD-S Series

Pr.

Explanation

Settings

Factory

NOTE

Setting

 

 

460V series: d4.0V to d510V

d24

 

1-05

Minimum Output Frequency (Fmin)

d1.0 to d60.0 Hz

d1.0

 

1-06

Minimum Output Voltage (Vmin)

230V series: d2.0V to d255V

d12.0

 

 

460V series: d4.0V to d510V

d24.0

 

 

 

 

1-07

Output Frequency Upper Limit

d1 to d110%

d100

 

1-08

Output Frequency Lower Limit

d0 to d100%

d0

 

1-09

Accel Time 1

d0.1 to d600 Sec

d10.0

 

1-10

Decel Time 1

d0.1 to d600 Sec

d10.0

 

1-11

Accel Time 2

d0.1 to d600 Sec

d10.0

 

1-12

Decel Time 2

d0.1 to d600 Sec

d10.0

 

1-13

Jog Acceleration / Deceleration Time

d0.1 to d600 Sec

d10.0

 

1-14

Jog Frequency

d1.0 Hz to d400 Hz

d6.0

 

 

 

d0: Linear Accel/Decel

 

 

 

 

d1: Auto Accel, Linear Decel

 

 

 

 

d2: Linear Accel, Auto Decel

 

 

1-15

Auto acceleration / deceleration (refer

d3: Auto Accel/Decel (Set by load)

d0

 

to Accel/Decel time setting)

d4: Linear Accel; Auto Decel, Stall

 

 

 

 

 

 

Prevention during Decel

 

 

 

 

d5: Auto Accel/Decel, Stall

 

 

 

 

Prevention during Decel

 

 

1-16

Acceleration S-Curve

d0 to d7

d0

 

1-17

Deceleration S-Curve

d0 to d7

d0

 

1-18

Jog Decelerating Time

d0.0 Jog Decelerating Time

d0.0

 

Determined by Pr.1-13

 

 

 

d0.1 to d600

 

 

Group 2 Operation Method Parameters

 

 

 

 

 

 

 

 

Pr.

Explanation

Settings

Factory

NOTE

Setting

 

 

d0: Master Frequency input

 

 

 

 

determined by digital keypad.

 

 

 

 

(record the frequency of power

 

 

 

 

loss and it can do analog

 

 

 

 

overlap plus)

 

 

 

 

d1: Master Frequency determined

 

 

 

 

by analog signal DC 0V-10V

 

 

 

 

(external terminal AVI). (won’t

 

 

 

 

record the frequency of power

 

 

 

 

loss and it can’t do analog

 

 

2-00

Source of Master Frequency

overlap plus)

d0

 

Command

d2: Master Frequency determined

 

 

 

 

 

 

by analog signal DC 4mA -

 

 

 

 

20mA (external terminal AVI).

 

 

 

 

(won’t record the frequency of

 

 

 

 

power loss and it can’t do

 

 

 

 

analog overlap plus)

 

 

 

 

d3: Master Frequency determined

 

 

 

 

by Potentiometer on the digital

 

 

 

 

keypad. (won’t record the

 

 

 

 

frequency of power loss and it

 

 

 

 

can do analog overlap plus)

 

 

Revision August 2006, SE08, SW V2.61

5-3

Page 60
Image 60
Delta Electronics 230V Series manual Explanation Settings Factory, Group 2 Operation Method Parameters Explanation Settings