Chapter 5 ParametersVFD-S Series

5.1 Summary of Parameter Settings

: The parameter can be set during operation.

Group 0 User Parameters

Pr.

Explanation

Settings

Factory

NOTE

Setting

0-00

Identity Code of the AC Motor Drive

Read-only

d #

 

0-01

Rated Current Display of the AC

Read-only

d##.#

 

 

Motor Drive

 

 

 

0-02

Parameter Reset

d09: All parameters are reset to

d0

 

 

 

factory settings (50Hz,

 

 

 

 

220V/380V)

 

 

 

 

d10: All parameters are reset to

 

 

 

 

factory settings (60Hz,

 

 

 

 

220V/440V)

 

 

 

 

d0: Display the frequency command

 

 

 

 

value (LED F)

 

 

 

 

d1: Display the actual output

 

 

 

 

frequency (LED H)

 

 

0-03

Start-up Display Selection

d2: Multifunction display, see Pr.00-

d0

 

 

 

04

 

 

 

 

d3: Display output current (LED A)

 

 

 

 

d4: Display forward/reverse

 

 

 

 

command (Frd/rEv)

 

 

 

 

d0: Display User-Defined Unit (u)

 

 

 

 

d1: Display Counter Value (C)

 

 

 

 

d2: Display Process Operation (1.tt)

 

 

0-04

Content of Multi-Function Display

d3: Display DC-BUS Voltage (u )

d0

 

d4: Display output voltage (E)

 

 

 

d5: Display frequency commands of

 

 

 

 

PID (P)

 

 

 

 

d6: Display analog feedback signal

 

 

 

 

value (b) (%)

 

 

0-05

User-Defined Coefficient K

d0.1 to d160

d1.0

 

0-06

Software Version

Read-only

d#.#

 

0-07

Password Input

d0 to d999

d0

 

0-08

Password Set

d0 to d999

d0

 

0-09

Memory Mode Selections

d0 to d63

d8

 

Group 1 Basic Parameters

 

 

 

 

 

 

 

 

Pr.

Explanation

Settings

Factory

NOTE

Setting

1-00

Maximum Output Frequency (Fmax)

d50.0 to d400 Hz

d60.0

 

 

 

 

 

 

1-01

Maximum Voltage Frequency (Fbase)

d10.0 to d400 Hz

d60.0

 

1-02

Maximum Output Voltage (Vmax)

230V series: d2.0V to d255V

d220

 

460V series: d4.0V to d510V

d440

 

 

 

 

1-03

Mid-Point Frequency (Fmid)

d1.0 to d400 Hz

d1.0

 

1-04

Mid-Point Voltage (Vmid)

230V series: d2.0V to d255V

d12

 

5-2

Revision August 2006, SE08, SW V2.61

Page 59
Image 59
Delta Electronics 115V Series manual Summary of Parameter Settings, Group 0 User Parameters Explanation Settings Factory