Chapter 5 ParametersVFD-S Series
Group 2: Operation Method Parameters
|
| Factory Setting: d0 |
Settings | d0 | Master Frequency input determined by digital keypad. (record the |
|
| frequency of power loss and it can do analog overlap plus) |
| d1 | Master Frequency determined by analog signal DC |
|
| (external terminal AVI). (won’t record the frequency of power loss |
|
| and it can’t do analog overlap plus) |
| d2 | Master Frequency determined by analog signal DC |
|
| (external terminal AVI). (won’t record the frequency of power loss |
|
| and it can’t do analog overlap plus) |
| d3 | Master Frequency determined by Potentiometer on the digital |
|
| keypad. (won’t record the frequency of power loss and it can do |
|
| analog overlap plus) |
| d4 | Master Frequency operated by |
|
| interface and record frequency of power loss. (record the frequency |
|
| of power loss and it can do analog overlap plus) |
| d5 | Master Frequency operated by |
|
| interface and won’t record frequency before power loss. (won’t |
|
| record the frequency of power loss and it can do analog overlap |
|
| plus) |
This parameter sets the Frequency Command Source of the AC drive.
If the Frequency Command Source is external (DC 0 to +10V or 4 to 20mA), please make
sure the (AVI) terminal jumper is in the proper position as shown below.
Position of jumper: Please open the top cover. It is at the
jumper J1 determines the type of external analog input, either DC voltage signal or current
signal.
J1
Voltage signal
Current signal
When setting analog overlap plus, it needs to set Pr.
Revision August 2006, SE08, SW V2.61 |