Weights

 

 

 

 

 

 

 

 

Bit

7

6

5

4

3

2

1

0

Direction

0

1

1

0

0

1

0

0

Chapter 5 ParametersVFD-S Series

0=Forward

1=Reverse

WD

Direction of 1st speed for Pr.5-00 =FWD

Direction of 2nd speed for Pr.5-01 =REV

Direction of 3rd speed for Pr.5-02 = FWD

Direction of 4th speed for Pr.5-03 = FWD

Direction of 5th speed for Pr.5-04 = FWD

Direction of 6th speed for Pr.5-05 = REV

Direction of 7th speed for Pr.5-06 = FWD

The setting value = bit7 x 27+bit6 x 26+bit5 x 25+bit4 x 24+bit3 x 23+bit2 x 22+bit1 x 21+bit0 x 20

=0 x 27+1 x 26+0 x 25+0 x 24+0 x 23+1 x 22+0 x 21+0 x 20

=0+64+0+0+0+4+0+0

=68

Setting Pr.5-08 as d68.

5-09

Time Duration of Zero Step Speed

Unit: 1

5-10

Time Duration of 1st Step Speed

Unit: 1

5-11

Time Duration of 2nd Step Speed

Unit: 1

5-12

Time Duration of 3rd Step Speed

Unit: 1

5-13

Time Duration of 4th Step Speed

Unit: 1

5-14

Time Duration of 5th Step Speed

Unit: 1

5-15

Time Duration of 6th Step Speed

Unit: 1

5-16

Time Duration of 7th Step Speed

Unit: 1

 

Settings

d0 to d65500

Factory Setting: d0

 

 

 

 

Pr.5-10 to Pr.5-16 correspond to operation time of each multi-step speed defined by parameters 5-00 to 5-06. The maximum value of these parameters is 65500 sec., and it’s displayed as d65.5.

NOTE

If a parameter is set to “d0” (0 Sec), the corresponding step will be skipped. This is commonly used to reduce number of program steps.

Revision August 2006, SE08, SW V2.61