Chapter 5 ParametersVFD-S Series

 

 

 

 

8-15

Automatic Voltage Regulation (AVR)

 

 

 

 

 

Factory Setting: d0

 

Settings

d0

AVR function enabled

 

 

d1

AVR function disabled

 

 

d2

AVR function disabled when deceleration

 

 

 

 

 

 

AVR function automatically regulates the AC drive output voltage to the Maximum Output Voltage (Pr.1-02). For instance, if Pr.1-02 is set at 200 VAC and the input voltage is at 200V to 264VAC, then the Maximum Output Voltage will automatically be reduced to a maximum of 200 VAC.

Without AVR function, the Maximum Output Voltage may vary between 180V to 264VAC, due to the input voltage varying between 180V to 264 VAC.

Selecting program value d2 enables the AVR function and also disables the AVR function during deceleration. This offers a quicker deceleration.

8-16

Software Braking Level

Unit: 1

 

 

 

 

 

Settings

230V series: d350 to d450V

Factory Setting: d380

 

 

460V series: d700to d900V

Factory Setting: d760

 

 

 

 

During deceleration, the DC-bus voltage will increase due to motor regeneration. When DC bus voltage level exceeds the Software Braking Level, the DC brake output pins (B1, B2) will be activated.

8-17

Lower Bound of DC Braking Start-up Frequency

Unit: 0.1

 

 

 

 

 

Settings

d0.0 to d400 Hz

Factory Setting: d0.0

 

 

 

 

The setting frequency is lower than Pr.8-17, the DC Braking will not be activated when stops.

Revision August 2006, SE08, SW V2.61