Chapter 5 ParametersVFD-S Series

Pr.

Explanation

Settings

Factory

NOTE

Setting

5-02

3rd Step Speed Freq.

d0.0 to d400 Hz

d0.0

 

5-03

4th Step Speed Freq.

d0.0 to d400 Hz

d0.0

 

5-04

5th Step Speed Freq.

d0.0 to d400 Hz

d0.0

 

5-05

6th Step Speed Freq.

d0.0 to d400 Hz

d0.0

 

5-06

7th Step Speed Freq.

d0.0 to d400 Hz

d0.0

 

 

 

d0: Disable PLC Operation

 

 

 

 

d1: Execute one program cycle

 

 

 

 

d2: Continuously execute program

 

 

 

 

cycles

 

 

 

 

d3: Execute one program cycle step

 

 

5-07

PLC Mode

by step

d0

 

 

 

d4: Continuously execute one

 

 

 

 

program cycle step by step

 

 

 

 

d5: Disable PLC operation, but can

 

 

 

 

set direction of 1st speed to 7th

 

 

 

 

speed

 

 

5-08

PLC Forward/ Reverse Motion

d0 to d255 (0: FWD 1: REV)

d0

 

5-09

Time Duration of Zero Step Speed

d0 to d65500 Sec

d0

 

5-10

Time Duration of 1st Step Speed

d0 to d65500 Sec

d0

 

5-11

Time Duration of 2nd Step Speed

d0 to d65500 Sec

d0

 

5-12

Time Duration of 3rd Step Speed

d0 to d65500 Sec

d0

 

5-13

Time Duration of 4th Step Speed

d0 to d65500 Sec

d0

 

5-14

Time Duration of 5th Step Speed

d0 to d65500 Sec

d0

 

5-15

Time Duration of 6th Step Speed

d0 to d65500 Sec

d0

 

5-16

Time Duration of 7th Step Speed

d0 to d65500 Sec

d0

 

Group 6 Protection Parameters

 

 

 

 

 

 

 

 

Pr.

Explanation

Settings

Factory

NOTE

Setting

6-00

Over-Voltage Stall Prevention

d0: Disable

d1

 

d1: Enable

 

 

 

 

 

6-01

Over-Voltage Stall Prevention Level

115V/230V series: d350 to d410V

d390

 

 

460V series: d700 to d820V

d780

 

 

 

 

6-02

Over-Current Stall Prevention Level

d20 to d150%

d130

 

 

 

d0: Disabled

 

 

 

 

d1: Enabled during constant speed

 

 

 

 

operation. After the over-torque

 

 

 

 

is detected, keep running until

 

 

 

 

OL1 or OL occurs.

 

 

 

 

d2: Enabled during constant speed

 

 

6-03

Over-Torque Detection Mode

operation. After the over-torque

d0

 

is detected, stop running.

 

 

 

d3: Enabled during running and

 

 

 

 

continues before Continuous

 

 

 

 

Output Time Limit (Pr.6-05) is

 

 

 

 

reached

 

 

 

 

d4: Enabled during running. After

 

 

 

 

the over-torque is detected, stop

 

 

 

 

running.

 

 

6-04

Over-Torque Detection Level

d30 to d200%

d150

 

Revision August 2006, SE08, SW V2.61

5-7

Page 64
Image 64
Delta Electronics 460V Series, 230V Series, 115V Series manual Group 6 Protection Parameters Explanation Settings