Chapter 5 ParametersVFD-S Series

Group A: PID Control

A-00Input Terminal for PID Feedback

Factory Setting: d0

Settings

d0

Disable

 

d1

Negative PID feedback from external terminal (AVI) 0 to +10V

 

d2

Negative PID feedback from external terminal (ACI) 4 to 20mA

 

d3

Positive PID feedback from external terminal (AVI) 0 to +10V

 

d4

Positive PID feedback from external terminal (ACI) 4 to 20mA

Select an input terminal to serve as the PID feedback location. Please verify the feedback location is different from the Frequency Set Point location and J1 for selecting ACI or AVI must be in the correct position. (Refer to Pr. 2-00 for detail)

Negative feedback = Positive target value – detection value.

Positive feedback = Negative target value + detection value.

A-01Gain over PID Detection value

Settings d0 to d999 (d100 means gain value is 1)Factory Setting: d100

To adjust feedback detective gain value. It is used to adjust target value error.

A-02

Proportional Gain (P)

Unit: 1

 

 

 

 

 

Settings

d0 to d999% (d0: disable) (d100 means

Factory Setting: d100

 

 

gain value is 1)

 

This parameter is used to determinate error gain. If I = 0 and D = 0, doing proportional gain

operation.

 

 

 

 

 

 

 

A-03

Integral Time (I)

 

Unit: 1

 

Settings

d0 to d999

Factory Setting: d100

 

 

d0

Disable

 

When this parameter is defined to gain is 1 and error value is fixed, integral value is equal to

error value as the setting of integral time is attained.

 

 

 

 

A-04

Derivative Control (D)

Unit: 1

 

Settings

d0 to d100

Factory Setting: d0

 

 

d0

Disable

 

Revision August 2006, SE08, SW V2.61

5-75