Chapter 5 ParametersVFD-S Series

ASCII mode:

LRC (Longitudinal Redundancy Check) is calculated by summing up, module 256, the values of the bytes from ADR1 to last data character then calculating the hexadecimal representation of the 2’s-complement negation of the sum.

For example, reading 1 word from address 0401H of the AC drive with address 01H

STX

‘:’

ADR 1

‘0’

ADR 0

‘1’

CMD1

‘0’

CMD0

‘3’

Starting data address

‘0’

 

‘4’

 

‘0’

 

‘1’

Number of data

‘0’

 

‘0’

 

‘0’

 

‘1’

LRC CHK 1

‘F’

LRC CHK 0

‘6’

END1

CR

END0

LF

01H+03H+04H+01H+00H+01H=0AH, the 2’s-complement negation of 0AH is F6H.

RTU mode:

ADR

01H

CMD

03H

Starting address

21H

 

02H

Number of data

00H

(count by word)

02H

CRC CHK Low

6FH

CRC CHK High

F7H

CRC (Cyclical Redundancy Check) is calculated by the following steps: Step 1: Load a 16-bit register (called CRC register) with FFFFH.

Step 2: Exclusive OR the first 8-bit byte of the command message with the low order byte of the 16-bit CRC register, putting the result in the CRC register.

Step 3: Examine the LSB of CRC register.

Step 4: If the LSB of CRC register is 0, shift the CRC register one bit to the right with MSB zero filling, then repeat step 3. If the LSB of CRC register is 1, shift the CRC register one bit to the right with MSB zero filling, Exclusive OR the CRC register with the polynomial value A001H, then repeat step 3.

Revision August 2006, SE08, SW V2.61

5-69

Page 126
Image 126
Delta Electronics 230V Series, 460V Series, 115V Series manual Starting data address ‘0’ ‘4’ ‘1’