4-10

Chapter 5 ParametersVFD-S Series

d29 M0: 0: RUN 1: STOP, M1: no function, Direction is controlled by keypad

RUN/STOP

M0 "Open": Stop, "Close": Run

M1 No Function

GND

4-09Line Start Lockout

 

 

Factory Setting: d0

Settings

d0

Disable

 

d1

Enable

When enabled, the AC drive will not start when powered up with run commands applied. To start in Line Start Lockout mode, the AC drive must see the run command go from stop to run after power up. When Line Start Lockout is disable (also known as Auto-Start), the drive will start when powered-up with run commands applied.

Up/Down Mode

 

 

 

 

 

Factory Setting: d0

 

 

Settings

d0

Based on accel/decel time

 

 

 

 

d1

up frequency according to constant speed, down frequency

 

 

 

 

according to deceleration time

 

 

 

 

d2

up frequency according to acceleration time, down frequency

 

 

 

 

according to constant speed

 

 

 

 

d3

Constant speed

 

 

 

 

 

 

 

 

 

 

4-11

Accel/Decel Rate of Change of UP/DOWN Operation

Unit: 5

 

with Constant Speed

 

 

 

 

 

 

 

Settings

d0 to d1000 Hz/sec

Factory Setting: d1

 

 

 

 

 

 

This parameter is used to set the acceleration/deceleration speed mode when multi-function terminal is set to up/down frequency. (Pr. 4-04 ~ Pr.4-08, function d15, d16)

5-46

Revision August 2006, SE08, SW V2.61

Page 103
Image 103
Delta Electronics 460V Series, 230V Series, 115V Series manual 09Line Start Lockout