Chapter 5 ParametersVFD-S Series

Content

Address

 

Functions

 

 

35: Reserved

 

 

36: PID error (Pld)

 

 

37: Reserved

 

 

38: Phase loss (PHL)

 

2101H

Status of AC Drive

 

 

 

00: RUN LED light off, STOP LED light up

 

 

Bit 0-1

01: RUN LED blink, STOP LED light up

 

 

10: RUN LED light up, STOP LED blink

 

 

 

 

 

 

11: RUN LED light up, STOP LED light off

 

 

Bit 2

01: Jog active

 

 

 

00: REV LED light off, FWD LED light up

 

 

Bit 3-4

01: REV LED blink, FWD LED light up

 

 

10: REV LED light up, FWD LED blink

 

 

 

 

 

 

11: REV LED light up, FRD LED light off

 

 

Bit 5-7

Not used

 

 

Bit 8

1: Main freq. Controlled by communication

 

 

Bit 9

1: Main freq. Controlled by external terminal

 

 

Bit 10

1: Operation command controlled by communication

 

 

Bit 11

1: Parameters have been locked

 

 

Bit 12-15

Not Used

 

2102H

Frequency

command F (XXX.XX)

 

2103H

Output Frequency H (XXX.XX)

 

2104H

Output Current A (XXX.XX)

 

2105H

DC-BUS Voltage U (XXX.XX)

 

2106H

Output Voltage E (XXX.XX)

 

2107H

Step number of Multi-Step Speed Operation

 

2108H

Step number of PLC operation

 

2109H

Time of PLC Operation

 

210AH

Counter Value

3.6 Exception response:

The AC motor drive is expected to return a normal response after receiving command messages from the master device. The following depicts the conditions when no normal response is replied to the master device.

The AC motor drive does not receive the messages due to a communication error; thus, the AC motor drive has no response. The master device will eventually process a timeout condition.

The AC motor drive receives the messages without a communication error, but cannot handle them. An exception response will be returned to the master device and an error message “CExx” will be displayed on the keypad of AC motor drive. The xx of “CExx” is a decimal code equal to the exception code that is described below.

In the exception response, the most significant bit of the original command code is set to 1, and an exception code which explains the condition that caused the exception is returned.

5-72

Revision August 2006, SE08, SW V2.61

Page 129