D.If the stall prevention function is activated, the accel./decel. time is automatically extended to a length that the AC Motor Drive can handle. If the motor needs to decelerate within a certain time with high load inertia that can’t be handled by the AC Motor Drive in the required time, either use an external brake resistor and/or brake unit, depending on the model, (to shorten deceleration time only) or increase the capacity for both the motor and the AC Motor Drive.
C.3 How to Choose a Suitable Motor
Standard motor
When using the AC Motor Drive to control a standard
A.The motor losses are greater than for an inverter duty motor.
B.Avoid running the motor at low speed for a long time. Under this condition, the motor temperature may rise above the motor rating due to limited airflow produced by the motor’s fan. Consider external forced motor cooling.
C.When the standard motor operates at low speed for long time, the output load must be decreased.
D.The load tolerance of a standard motor is as follows:
Load
torque(%)
25% 40% 60%
100
82
70 |
|
60 | continuous |
50 |
0 | 3 6 | 20 | 60 |
|
Frequency (Hz)
Revision August 2006, SE08, SW V2.61 |