Chapter 5 ParametersVFD-S Series

Example 5 (Pr. 5-07 = d1 Execute one cycle of the PLC program):

In this example, the PLC program runs continuously. It should be noted that the times of reserve

motion may be shorter than expected, due to the acceleration/deceleration times.

Frequency

 

Master freq.=5Hz

 

60Hz

5-00=10 Hz

4-07=d17

5-09=10 Sec

 

5-01=20 Hz

3-05=d10

5-10=10 Sec

50Hz

5-02=40 Hz

3-06=d11

5-11=12 Sec

5-03=60 Hz

5-07=d1

5-12=15 Sec

 

5-04=50 Hz

5-08=d68

5-13=15 Sec

40Hz

5-05=30 Hz

 

5-14=8 Sec

 

5-06=15 Hz

 

5-15=17 Sec

 

 

 

5-16=17 Sec

FWD

 

 

 

15Hz

 

 

 

10Hz

 

 

 

0Hz

 

 

Time

 

 

 

(Sec)

REV

5-09

 

 

 

 

 

20Hz

 

 

 

30Hz

 

 

 

 

* The calculation of time for Pr.5-11, Pr.5-12, Pr.5-15 and Pr.5-16 should be carefully planned.

5-08

PLC Forward/Reverse Motion

Unit: 1

 

Settings

d0 to d255

Factory Setting: d0

 

 

 

 

This parameter controls the direction of motion for the Multi-Step Speed Pr.5-00 to Pr.5-06 and the Master Frequency. The original direction of Master Frequency will become invalid.

NOTE

The equivalent 8-bit number is used to program the forward/reverse motion for each of the 8 speed steps (including Master Frequency). The binary notation for the 8-bit number must be translated into decimal notation and then be entered.

Weights

 

 

 

 

 

 

 

0=Forward

Bit

7

6

5

4

3

2

1

1=Reverse

0

Director of Master Frequency during PLC

Direction of 1st speed for Pr.5-00

Direction of 2nd speed for Pr.5-01

Direction of 3rd speed for Pr.5-02

Direction of 4th speed for Pr.5-03

Direction of 5th speed for Pr.5-04

Direction of 6th speed for Pr.5-05

Direction of 7th speed for Pr.5-06

5-50

Revision August 2006, SE08, SW V2.61

Page 107
Image 107