2-03

PWM Carrier Frequency Selections

Unit: 1

 

115V/230V/460V Series

Power

0.25 to 3hp (0.2kW to 2.2kW)

Setting Range

d3 to d10 kHz

Factory Setting

d10 kHz

This parameter determines the PWM carrier frequency of the AC motor drive.

Carrier

Acoustic

Electromagnetic

Heat

Current

Frequency

Noise

Noise or leakage

Dissipation

Wave

 

 

current

 

 

3kHz

Significant

Minimal

Minimal

Minimal

 

 

 

 

10kHz

Minimal

Significant

Significant

Significant

From the table, we see that the PWM carrier frequency has a significant influence on the electromagnetic noise, AC motor drive heat dissipation, and motor acoustic noise.

2-04Motor Direction Control

 

 

Factory Setting: d0

Settings

d0

Enable forward/reverse operation

 

d1

Disable reverse operation

 

 

 

The parameter determines whether the AC drive can operate in the reverse direction.