Chapter 5 ParametersVFD-S Series
| ||||
|
|
|
| Factory Setting: d0 |
| Settings | d0 | Disable | |
|
| d1 | 1 sec | |
|
| d2 | 2 sec | |
|
| : |
|
|
|
| d20 | 20 sec | |
|
|
|
|
|
If this function is enabled, the timer will start counting once the first valid Modbus
communication signal is received after
valid Modbus communication message is received. If the watchdog timer reaches the value
set in Pr.
keypad. This fault can reset by an external terminal, keypad or a Modbus communication
reset command.
Factory Setting: d0
Settings | d0 | Modbus ASCII mode, protocol <7,N,2> | |||||||||
| d1 | Modbus ASCII mode, protocol <7,E,1> | |||||||||
| d2 | Modbus ASCII mode, protocol <7,O,1> | |||||||||
| d3 | Modbus ASCII mode, protocol <8,N,2> | |||||||||
| d4 | Modbus ASCII mode, protocol <8,E,1> | |||||||||
| d5 | Modbus ASCII mode, protocol <8,O,1> | |||||||||
| d6 | Modbus RTU mode, protocol <8,N,2> | |||||||||
| d7 | Modbus RTU mode, protocol <8,E,1> | |||||||||
| d8 | Modbus RTU mode, protocol <8,O,1> | |||||||||
|
|
|
|
|
|
|
|
|
|
| |
1. Computer Control |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
| 1: +EV |
|
|
|
|
|
|
|
|
|
|
| 2: GND |
|
|
|
|
|
|
|
|
|
|
| 3: SG- |
|
|
|
|
|
|
|
|
|
|
| 4: SG+ |
|
|
|
|
|
|
| |||||
|
| 6 | 1 |
There is a
Revision August 2006, SE08, SW V2.61 |