Chapter 5 ParametersVFD-S Series

3.2 ADR (Communication Address)

Valid communication addresses are in the range of 0 to 254. A communication address equal to 0, means broadcast to all AC drives (AMD). In this case, the AMD will not reply any message to the master device.

00H: broadcast to all AC drives

01H: AC drive of address 01

0FH: AC drive of address 15

10H: AC drive of address 16

:

FEH: AC drive of address 254

For example, communication to AMD with address 16 decimal (10H): ASCII mode: Address=’1’,’0’ => ‘1’=31H, ‘0’=30H

RTU mode: Address=10H

3.3 CMD (Command code) and DATA (data characters)

The format of data characters depends on the command code. The available command codes are described as followed: Command code: 03H, read N words. The maximum value of N is 12. For example, reading continuous 2 words from starting address 2102H of

AMD with address 01H.

ASCII mode:

Command message:

STX

‘:’

ADR 1

‘0’

ADR 0

‘1’

CMD 1

‘0’

CMD 0

‘3’

 

 

Starting data

‘2’

‘1’

address

‘0’

 

‘2’

Number of data

‘0’

‘0’

(count by word)

‘0’

 

‘2’

LRC CHK 1

‘D’

LRC CHK 0

‘7’

END 1

CR

END 0

LF

Response message:

STX

‘:’

ADR 1

‘0’

ADR 0

‘1’

CMD 1

‘0’

CMD 0

‘3’

 

 

Number of data

‘0’

(Count by byte)

‘4’

Content of starting

‘1’

‘7’

address

‘7’

2102H

‘0’

 

Content of address

‘0’

‘0’

2103H

‘0’

 

‘0’

LRC CHK 1

‘7’

LRC CHK 0

‘1’

END 1

CR

END 0

LF

5-66

Revision August 2006, SE08, SW V2.61

Page 123
Image 123
Delta Electronics 230V Series, 460V Series, 115V Series manual Lrc Chk