Delta Electronics 115V Series, 230V Series, 460V Series manual Over Heat OH, Overload

Models: 230V Series 460V Series 115V Series

1 187
Download 187 pages 5.92 Kb
Page 143
Image 143

Chapter 7 Troubleshooting VFD-S Series

7.5 Over Heat (OH)

AC motor drive overheats

Heat sink overheats

Check if temperature of heat sink No is greater than 90 OC

Yes

Temperature detection malfunctions. Please contact DELTA.

Is load too large

Yes

 

 

 

Reduce load

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

If cooling fan functions normally

 

 

 

 

 

 

 

 

Change cooling fan

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

Remove obstruction

Check if cooling fan is jammed

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check if surrounding temperature

No

 

 

 

Maybe AC motor drive has malfunction or

is within specification

 

 

 

 

 

 

 

misoperation due to noise. Please contact

 

 

 

 

 

 

 

DELTA.

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjust surrounding temperature

 

 

 

 

 

 

 

 

 

to specification

 

 

 

 

 

 

 

 

 

7.6 Overload

OL

OL1/ OL2

Check for correct settings at Pr. 06-06 and 06-07

 

Yes

 

 

 

No

Is load too large

 

 

Yes

 

 

 

 

 

 

No

Modify setting

 

Maybe AC motor drive has malfunction or misoperation due to noise.

Reduce load or increase the power of AC motor drive

7-4

Revision August 2006, SE08, SW V2.61