Chapter 5 ParametersVFD-S Series

Pr.

Explanation

Settings

Factory

NOTE

Setting

A-07

PID Output Freq. Limit

d0 to d110%

d100

 

 

 

 

 

 

A-08

Feedback Signal Detection Time

d0.0 to d650 seconds

d0.0

 

 

 

 

 

 

A-09

Treatment of the Erroneous

d0: warn and RAMP to stop

d0

 

Feedback Signals

d1: warn and COAST to stop

 

 

 

 

 

 

 

 

 

A-10

Sleep Frequency

d0.0 to d400Hz

d0.0

 

A-11

Wakeup Frequency

d0.0 to d400Hz

d0.0

 

A-12

Sleep Period

d0.0 to d650 seconds

d0.0

 

A-13

PID User Defined

d0.0 to d400

d0.0

 

Revision August 2006, SE08, SW V2.61

5-11

Page 68
Image 68
Delta Electronics 115V Series, 230V Series, 460V Series manual Explanation Settings Factory