Chapter 2 Installation and WiringVFD-S Series

Terminal

Terminal Function

 

Factory Settings (NPN mode)

Symbol

 

ON: Connect to GND

 

 

 

 

0~+10V/4-20mA corresponds to 0-max.

 

 

operation frequency (Pr.01-00)

 

 

PID feedback signal

 

 

AVI input impedance: 100kohm

 

 

ACI input impedance: 250kohm

 

 

AVI

+10V

AVI circuit

 

 

ACI

 

 

 

 

 

 

J1

 

 

 

Analog voltage Input

 

AVI

 

 

(AVI/ACI)

 

 

AVI

 

 

 

 

 

 

 

 

 

 

GND

Internal Circuit

 

 

 

 

 

 

AVI

 

ACI circuit

 

 

ACI

ACI

 

 

 

 

 

J1

 

 

 

 

 

GND

Internal Circuit

Control signal wiring size: 18 AWG (0.75 mm2) with shielded wire.

Analog input terminals (AVI, GND)

Analog input signals are easily affected by external noise. Use shielded wiring and keep it as short as possible (<20m) with proper grounding. If the noise is inductive, connecting the shield to terminal GND can bring improvement.

If the analog input signals are affected by noise from the AC motor drive, please connect a capacitor (0.1 μ F and above) and ferrite core as indicated in the following diagrams:

AVI

C

GND

ferrite core

wind each wires 3 times or more around the core Digital inputs (M0~M5, GND)

When using contacts or switches to control the digital inputs, please use high quality components to avoid contact bounce.

2-26

Revision August 2006, SE08, SW V2.61

Page 41
Image 41
Delta Electronics 115V Series, 230V Series, 460V Series manual Avi/Aci