Chapter 2 Installation and
2.4.3 Main Terminals Connections
Terminal Symbol | Explanation of Terminal Function | |||||||
|
|
|
|
|
|
|
| |
R/L1, S/L2, T/L3 | AC line input terminals | |||||||
|
|
|
|
|
|
|
| |
L/L1, N/L2 | AC line input terminals | |||||||
|
|
|
|
|
|
|
| |
U/T1, V/T2, W/T3 | AC drive output terminals for connecting | |||||||
induction motor | ||||||||
|
|
|
|
|
|
| ||
+2/B1, B2 | Connections for Brake resistor (optional) | |||||||
|
|
|
|
|
|
|
| |
+2/B1, +1 | Connections for DC Link Reactor (optional) | |||||||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| Earth connection, please comply with local regulations. | |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
Mains power terminals (R/L1, S/L2, T/L3 and L/L1, N/L2)
Connect these terminals via a
It is recommended to add a magnetic contactor (MC) in the power input wiring to cut off power quickly and reduce malfunction when activating the protection function of AC motor drives. Both ends of the MC should have an
Do NOT run/stop AC motor drives by turning the power ON/OFF. Run/stop AC motor drives by RUN/STOP command via control terminals or keypad. If you still need to run/stop AC drives by turning power ON/OFF, it is recommended to do so only ONCE per hour.
Do NOT connect
Control circuit terminals (U/T1, V/T2, W/T3)
When the AC drive output terminals U/T1, V/T2, and W/T3 are connected to the motor terminals U/T1, V/T2, and W/T3, respectively, the motor will rotate counterclockwise (as viewed on the shaft end of the motor) when a forward operation command is received. To permanently reverse the direction of motor rotation, switch over any of the two motor leads.
Forward running