Delta Electronics VFD-F Series V/F Curve Diagram, Circulative Control, Settings, No function

Models: VFD-F Series

1 161
Download 161 pages 45.18 Kb
Page 96
Image 96
V/F Curve Diagram
VFD-F Series
Factory Setting: 00

5.12 Group 11: Fan and Pump Control Parameters

11 - 00 V/f Curve Selection

Settings

00: Determined by group 1

 

01: 1.5 power curve

 

02:

1.7 power curve

 

03:

2 power curve

04: cube curve

This parameter is to set V/f curve. If this parameter isn’t set to 00, parameter 01-03 and 01-04 will disable.

Input current of the motor could divide into two orthogonal vectors: magnetic vector and torque vector. Gap flux, which is produced by Magnetic vector, is in direct proportion with output voltage of motor. Torque vector produces torque. Torque is in direct proportion with the result of magnetic vector multiply by torque vector. In theory, if the value of magnet vector is the same with torque vector (in unsaturated flux condition), the input current is minimum. If motor loading is unsteady torque loading (loading torque is in direct proportion with speed. For example, the loading of fan or pump), loading torque is low during low speed, suitable lower input voltage will decrease input current of magnetic field to lower flux loss and iron loss of the motor and promote whole efficiency.

When this parameter is set to high power V/f curve and low frequency torque is lower, it is not suitable for AC drive to accel/decel quickly. If it needs to accel/decel quickly, it is not recommended to use this parameter.

 

01-02Voltage%

100

1.5 power curve

90

80

1.7 power curve

70

 

602 power curve

 

 

50

 

3 power curve

 

 

 

 

 

 

 

40

 

 

 

 

Frequency

 

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

%

 

 

 

20

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

01-01

 

 

 

0

20

 

40

60

80

100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V/F Curve Diagram

 

 

 

 

 

 

 

 

 

 

 

11 - 01

Circulative Control

 

 

 

 

 

 

Factory Setting: 00

 

Settings

00: No function

 

 

 

 

 

 

 

01: Time circulation (by time)

 

 

 

02: Fixed amount circulation (by PID)

03: Fixed amount control (an AC drive runs with 4 motors)

This parameter is to set an AC drive runs with multiple motors in circulation control mode.

DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED

5-63

5

Page 96
Image 96
Delta Electronics VFD-F Series V/F Curve Diagram, Circulative Control, Settings, No function, Time circulation by time