01 - 19 | JOG Frequency |
| Factory Setting: 6.00 | |
|
|
|
|
|
| Settings | 0.0 Hz~120.00 Hz | Unit: 0.1sec |
When the JOG function is to be utilized, users need to use the
The accel/decel time of the JOG operation is determined by the JOG accel/decel speed
When the drive is in operation, the JOG command is disabled.
01 - 20 | S Curve Delay Time in Accel | Factory Setting: 0.00 | |
01 - 21 | S Curve Delay Time in Decel |
| |
| Settings | 0.00~2.50sec |
|
These parameters enable the S curve. The longer the S curve time period the smoother the transition between speeds.
01 - 22 | Modulation Index |
| Factory Setting: 1.00 | |
|
|
|
|
|
| Settings | 0.90~1.20 |
| Unit: 0.1 |
This parameter sets the ratio of the Maximum Output Voltage to the input voltage.
The Maximum Output Voltage
A Modulation Index of 1, defines the Maximum Output Voltage (Pr.
A Modulation index of 1.2, defines the Maximum Output Voltage (Pr.
01 - 23 Accel/Decel Time Unit
Settings | 00: Unit is 1 Sec |
| 01: Unit is 0.1 Sec |
| 02: Unit is 0.01 Sec |
This parameter sets the resolution of accel/decel time
A high resolution decreases the accel/decel time range as shown in the following chart.