Delta Electronics VFD-F Series manual Please refer to the following diagram for more details

Models: VFD-F Series

1 161
Download 161 pages 45.18 Kb
Page 55
Image 55
Please refer to the following diagram for more details:

Manual background VFD-F Series

Please refer to the following diagram for more details:

01-00,10-10

04-12

04-16

04-11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04-15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04-19

 

 

 

 

 

 

 

 

 

 

04-09

 

04-10

 

 

 

 

 

04-13

 

04-14

 

 

 

 

 

 

 

 

 

 

04-17

 

04-18

 

Analog

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

input

Example: Using the AVI(0~10V) as the target source and ACI1(4~20mA corresponds to 0~5Pa) and ACI2(0~10mA corresponds to 0~4Pa) as the feedback location for a pressure sensor connected. If your target value is between 3~7Pa (Set Pr.10-01 to 10, other parameters settings refer Pr.10-01 to set as shown in the following diagram and then setting the PID feedback relative parameters.) If setting AVI to 7.5V, pressure sum of ACI1 and ACI2 could be controlled at 6Pa.

Pressure Pa

 

10-10=10.0 Pa

 

 

04-12=70

 

 

 

04-16=50

 

AVI

 

 

ACI2

 

04-20=40

 

 

 

 

 

04-11=30

 

ACI1

 

 

 

 

04-15=0

 

 

 

04-19=0

 

 

Analog

 

 

 

input

04-9=0V 04-13=4mA

04-18=10mA

 

04-17=0mA

 

 

When analog input current of ACI1/ACI2 is lower than Pr.04-13/Pr.04-17, EF warning will pup-up.