Fluke 2625A, 2635A 5A-10. Analog Troubleshooting, Power Supply Test Location Acceptable Range

Models: 2635A 2625A

1 310
Download 310 pages 12.8 Kb
Page 211
Image 211

Diagnostic Testing and Troubleshooting (2635A) 5A

Analog Troubleshooting

Note

When making voltage measurements in the invertercircuit, remember that there are two separategrounds. The outguard ground is the ’GND’ testpoint (A1TP1), and the inguard ground is the’COM’ test point (A1TP30).

The inguard regulator circuits for VDD and VSS have current limits. Shorts and heavy loads between VDD and COM, VSS and COM, and VDD and VSS will cause one or both supplies to go into current limit. The current supplied by either supply can be checked by measuring the voltage across the current sense resistors, A1R13 and A1R15. The typical voltage across A1R13 is 0.30, and the typical voltage across A1R15 is 0.40V.

Generally, open electrolytic capacitors in the inverter supply will cause excessive ripple for the affected supply. Also, the rectified dc voltage for the supply with the open capacitor will be lower than normal. Normal voltage levels at the rectifier outputs for each inverter supply are shown in Table 5A-2.

The loads for the inguard supplies can be disconnected by removing the cable to the A/D Converter PCA at A3J10. The inguard regulator circuits and VDDR regulator will operate with no loads, and troubleshooting can be performed by making voltage measurements.

The normal input current to the inverter supply is about 11.25 mA, or 0.225 mV across A1R38 (when the instrument is not measuring).

Table 5A-3 provides a Power Supply troubleshooting guide.

5A-10. Analog Troubleshooting

Warning

To avoid electric shock, disconnect all channelinputs from the instrument before performing anytroubleshooting operations.

Refer to Figure 5A-4 and Figure 5A-5 for test point locations on the A/D Converter PCA.

First, check for analog-related errors displayed at power up. An ’Error 9’ means that the Main Microprocessor A1U1 is not able to communicate with the A/D Microcontroller A3U9. ’Error A’ and ’Error b’ mean that a failure has occurred in the internal memory of the A/D Microcontroller A3U9. ’Error C’ means that the Analog Measurement Processor A3U8 is not functioning properly.

Check the inguard power supplies on the Main PCA with and without the A/D Converter PCA connected. The inguard supplies must be measured with respect to COM testpoint A1TP30.

Power Supply

Test Location

Acceptable Range

VDD

A1TP31

5.00 to 5.70V dc

VSS

A1TP32

-5.10 to -5.75V dc

VDDR

A1C6+

5.30 to 5.95V dc

5A-11

Page 211
Image 211
Fluke 2625A, 2635A service manual 5A-10. Analog Troubleshooting, Power Supply Test Location Acceptable Range