Table 26. LONMARK® /Open System Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

DigitalStateor ValueofState

Default

E-Vision(M,P,S)

Share

Map

DirectAccess

HardwareConfig.

ManualConfig.

FailureDetect

Comments

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DestEmergCmd

nviEmerg

 

EMERG_NORMAL

0

EMERG_NORMAL

M

X

X

X

 

X

 

Emerg is an emergency input from a device that determines the correct

 

 

(SNVT_hvac_emerg)

 

EMERG_PRESSURIZE

1

 

 

 

 

 

 

 

 

action during a given emergency (such as a fire). If Emerg is

 

 

 

 

EMERG_DEPRESSURIZE

2

 

 

 

 

 

 

 

 

EMERG_NORMAL the fan and economizer damper are controlled by the

 

 

 

 

EMERG_PURGE

3

 

 

 

 

 

 

 

 

heating and cooling control algorithm. If Emerg is EMERG_PRESSURIZE,

 

 

 

 

EMERG_SHUTDOWN

4

 

 

 

 

 

 

 

 

then the fan is controlled on and the economizer damper is open. If Emerg

 

 

 

 

EMERG_NUL

255

 

 

 

 

 

 

 

 

is EMERG_DEPRESSURIZE, then the fan is controlled on and the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

economizer damper is closed. If Emerg is EMERG_SHUTDOWN, then the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fan is controlled off and the economizer damper is closed. If Emerg is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EMERG_PURGE, the fan and damper go to the state specified by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Config.SmokeControl. If Emerg is not configured then it is set to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EMERG_NUL.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SrcUnitStatus

nvoUnitStatus

mode

HVAC_AUTO

0

HVAC_NUL

M

X

 

X

 

 

 

Mode is set according to the Data1.mode. If Data1.mode is

 

 

(SNVT_hvac_status)

 

HVAC_HEAT

1

 

 

 

 

 

 

 

 

START_UP_WAIT, SMOKE_EMERGENCY, or FREEZE_PROTECT, mode

 

 

 

 

HVAC_MRNG_WRMUP

2

 

 

 

 

 

 

 

 

is set to HVAC_NUL which indicates that the node is in a mode not

 

 

 

 

HVAC_COOL

3

 

 

 

 

 

 

 

 

supported by the SNVT_hvac_mode data type. If Data1.mode is HEAT,

 

 

 

 

HVAC_NIGHT_PURGE

4

 

 

 

 

 

 

 

 

then mode is set to HVAC_HEAT which indicates that heating energy is

 

 

 

 

HVAC_PRE_COOL

5

 

 

 

 

 

 

 

 

being supplied to the controlled space. If Data1.mode is COOL, then mode

 

 

 

 

HVAC_OFF

6

 

 

 

 

 

 

 

 

is set to HVAC_COOL, which indicates that cooling energy is being

101

 

 

 

HVAC_TEST

7

 

 

 

 

 

 

 

 

supplied to the controlled space. If Data1.mode is OFF_MODE or

 

 

 

HVAC_EMERG_HEAT

8

 

 

 

 

 

 

 

 

DISABLED_MODE, then mode is set to HVAC_OFF which indicates that

 

 

 

 

HVAC_FAN_ONLY

9

 

 

 

 

 

 

 

 

the node is not running its normal temperature control and the outputs are

 

 

 

 

HVAC_NUL

255

 

 

 

 

 

 

 

 

not turned off. If Data1.mode is EMERG_HEAT, mode is set to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HVAC_EMERG_HEAT where, in a heat pump application, the compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

stages are disabled and only auxiliary heating stages are turned on. If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data1.mode is MANUAL or FACTORY_TEST, mode is set to HVAC_TEST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

which indicates that the node is in a manual or test mode. If Data1.mode is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN_ONLY, mode is set to HVAC_FAN_ONLY which indicates that the fan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is running but the space temperature control is turned off.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoUnitStatus

heat_output_primary

Percentage

 

0

 

 

 

 

 

 

 

heat_output_primary reports the current percentage of heating stages or

 

 

(SNVT_hvac_status)

 

0 to 100

 

 

 

 

 

 

 

 

 

modulating heat turned on. If the node is controlling a heat pump,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heat_output_primary reports the current percentage of compressor stages

 

 

 

 

 

 

 

 

 

 

 

 

 

 

turned on when the node is in the HVAC_HEAT mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoUnitStatus

heat_output_secondary

Percentage

 

0

 

 

 

 

 

 

 

If the node is controlling a heat pump, heat_output_secondary reports the

 

 

(SNVT_hvac_status)

 

0 to 100

 

 

 

 

 

 

 

 

 

current percentage of auxiliary heating stages turned on when the node is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in the HVAC_HEAT or HVAC_EMERG_HEAT mode. If the node is not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controlling a heat pump, heat_output_secondary is set to zero.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoUnitStatus

cool_output

Percentage

 

0

 

 

 

 

 

 

 

cool_output reports the current percentage of cooling stages or modulating

 

 

(SNVT_hvac_status)

 

0 to 100

 

 

 

 

 

 

 

 

 

cool turned on. If the node is controlling a heat pump, cool_output reports

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the current percentage of compressor stages turned on when the node is in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the HVAC_COOL mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoUnitStatus

econ_output

Percentage

 

0

 

 

 

 

 

 

 

If there is a modulating economizer configured, econ_output reports the

 

 

(SNVT_hvac_status)

 

0 to 100

 

 

 

 

 

 

 

 

 

percentage that the economizer damper is opened. If no economizer is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

configured, econ_output reports 0.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoUnitStatus

fan_output

Percentage

 

0

 

 

 

 

 

 

 

When the fan is running, fan_output is 100 percent, and when the fan is not

74-2958— 1

 

(SNVT_hvac_status)

 

0 to 100

 

 

 

 

 

 

 

 

 

running, fan_output is 0 percent.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER