Table 23. Status Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value

Digital

 

E-Vision

 

 

Direct

Hardware

Manual

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

ofState

Stateor

Default

(M, P,S)

Share

Map

Access

Config.

Config.

Test

Comments

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

MonitorSens

nvoCtlDataG2

siMonitor1S10

volts

 

 

SI_INVALID

 

 

X

 

 

 

 

siMonitor1S10: siMonitor1S10 is the voltage applied at the monitor input

 

 

 

1 to 10

 

 

 

 

 

 

 

 

 

 

terminals. If the sensor is not configured or has failed, the value is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SI_INVALID.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CoolPos

nvoCtlDataG2

sbCoolPosS0

Percentage

 

 

0

 

 

X

 

 

 

 

sbCoolPosS0: If the node is configured for modulating cool, sbCoolPosS0

 

 

 

0 to 100

 

 

 

 

 

 

 

 

 

 

shows the current position of the cooling modulating output.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HeatPos

nvoCtlDataG2

sbHeatPosS0

Percentage

 

 

0

 

 

X

 

 

 

 

sbHeatPosS0: If the node is configured for modulating heat, sbHeatPosS0

 

 

 

0 to 100

 

 

 

 

 

 

 

 

 

 

shows the current position of the heating modulating output.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EconPos

nvoCtlDataG2

sbEconPosS0

Percentage

 

 

0

 

 

X

 

 

 

 

sbEconPosS0: If the node is configured for modulating economizer,

 

 

 

0 to 100

 

 

 

 

 

 

 

 

 

 

sbEconPosS0 shows the current position of the economizer modulating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

StatusError

nvoError

error_bit[0]

FALSE

0

 

FALSE

 

 

 

X

 

 

 

For SpaceTempError, a value of 1 (TRUE) indicates that data was not

 

 

Byte Offset = 0

TRUE

1

 

 

 

 

 

 

 

 

 

available from the sensor and will result in a SENSOR_FAILURE alarm. A

 

 

Bit Offset = 0

 

 

 

 

 

 

 

 

 

 

 

value of 0 (FALSE) indicates a normal condition. The heating and cooling

 

 

(SpaceTempError)

 

 

 

 

 

 

 

 

 

 

 

control loops will be turned off it there is a space temp sensor failure. The

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fan will remain under normal control.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[0]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

For SetPtError, see preceding. Upon a failure of the local setpoint, the

 

 

Byte Offset = 0

TRUE

1

 

 

 

 

 

 

 

 

 

control loop will use the default occupied setpoints to control space

 

 

Bit Offset = 1

 

 

 

 

 

 

 

 

 

 

 

temperature.

 

 

(SetPtError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[0]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

For OdTempError, see preceding. All control functions associated with the

 

 

Byte Offset = 0

TRUE

1

 

 

 

 

 

 

 

 

 

failed sensor are disabled as if the sensor was not configured.

 

 

Bit Offset = 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(OdTempError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[0]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

For OdHumError, see preceding. A value of 0 (FALSE) indicates a normal

 

 

Byte Offset = 0

TRUE

1

 

 

 

 

 

 

 

 

 

condition. All control functions associated with the failed sensor are

 

 

Bit Offset = 3

 

 

 

 

 

 

 

 

 

 

 

disabled as if the sensor was not configured.

 

 

(OdHumError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[0]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

OdEnthalpyError: All control functions associated with the failed sensor are

 

 

Byte Offset = 0

TRUE

1

 

 

 

 

 

 

 

 

 

disabled as if the sensor was not configured.

 

 

Bit Offset = 4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(OdEnthalpyError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[0]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

DischgTempError: All control functions associated with the failed sensor are

 

 

Byte Offset = 0

TRUE

1

 

 

 

 

 

 

 

 

 

disabled as if the sensor was not configured.

 

 

Bit Offset = 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(DischgTempError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[0]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

RtnTempError: All control functions associated with the failed sensor are

 

 

Byte Offset = 0

TRUE

1

 

 

 

 

 

 

 

 

 

disabled as if the sensor was not configured.

 

 

Bit Offset = 6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RtnTempError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nvoError

error_bit[0]

FALSE

0

 

FALSE

 

 

 

 

 

 

 

RtnHumError: All control functions associated with the failed sensor are

 

 

Byte Offset = 0

TRUE

1

 

 

 

 

 

 

 

 

 

disabled as if the sensor was not configured.

 

 

Bit Offset = 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(RtnHumError)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER