Table 26. LONMARK® /Open System Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

DigitalStateor ValueofState

Default

E-Vision(M,P,S)

Share

Map

DirectAccess

HardwareConfig.

ManualConfig.

FailureDetect

Comments

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DestHvacMode

nviApplMode

 

HVAC_AUTO

0

HVAC_AUTO

M

X

X

X

 

X

X

ApplMode is an input that coordinates the roof top unit controller operation

 

 

(SNVT_hvac_mode)

 

HVAC_HEAT

1

 

 

 

 

 

 

 

 

with other controllers. HVAC_NIGHT_PURGE

 

 

 

 

HVAC_MRNG_WRMUP

2

 

 

 

 

 

 

 

 

HVAC_PRE_COOL

 

 

 

 

HVAC_COOL

3

 

 

 

 

 

 

 

 

HVAC_MRNG_WRMUP

 

 

 

 

HVAC_NIGHT_PURGE

4

 

 

 

 

 

 

 

 

HVAC_NUL

 

 

 

 

HVAC_PRE_COOL

5

 

 

 

 

 

 

 

 

HVAC_TEST are not supported and will default to the HVAC_AUTO setting

 

 

 

 

HVAC_OFF

6

 

 

 

 

 

 

 

 

if received.

 

 

 

 

HVAC_TEST

7

 

 

 

 

 

 

 

 

 

 

 

 

 

HVAC_EMERG_HEAT

8

 

 

 

 

 

 

 

 

 

 

 

 

 

HVAC_FAN_ONLY

9

 

 

 

 

 

 

 

 

 

 

 

 

 

HVAC_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DestManOcc

nviManOcc

 

OC_OCCUPIED

0

OC_NUL

 

X

 

X

 

X

 

ManOcc is an input from a network connected operator interface or other

 

 

(SNVT_occupancy)

 

OC_UNOCCUPIED

1

 

 

 

 

 

 

 

 

node that indicates the state of a manual occupancy control thus over

 

 

 

 

OC_BYPASS

2

 

 

 

 

 

 

 

 

riding the scheduled occupancy state. ManOcc is used along with other

 

 

 

 

OC_STANDBY

3

 

 

 

 

 

 

 

 

occupancy inputs to calculate the effective occupancy of the node. See the

 

 

 

 

OC_NUL

255

 

 

 

 

 

 

 

 

Data1.EffectOcc and Data1.NetManOcc for more details.The valid

 

 

 

 

 

 

 

 

 

 

 

 

 

 

enumerated values have the following meanings: OC_OCCUPIED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

indicates occupied. OC_UNOCCUPIED indicates not occupied.

99

 

 

 

 

 

 

 

 

 

 

 

 

 

OC_BYPASS indicates that the space is occupied for

 

 

 

 

 

 

 

 

 

 

 

 

 

Aux2SetPt.BypassTime seconds after ManOcc is first set to OC_BYPASS.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The timing is done by the bypass timer in this node. If ManOcc changes to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

another value the timer is stopped.OC_STANDBY indicates that the space

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is in standby mode.OC_NUL and all unspecified values means that no

 

 

 

 

 

 

 

 

 

 

 

 

 

 

manual occupancy control is requested. When ManOcc changes from

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OC_OCCUPIED, OC_UNOCCUPIED, OC_BYPASS, or OC_STANDBY to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OC_NUL, any bypass condition is canceled.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DestRmTempSpt

nviSetPoint

 

Degrees F

 

SI_INVALID

 

X

 

X

 

X

 

SetPoint is an input network variable used to determine the temperature

 

 

(SNVT_temp_p)

 

50 to 95

 

 

 

 

 

 

 

 

 

control point of the node. If SetPoint is not SI_INVALID, then it is used to

 

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

determine the control point of the node. If SetPoint is SI_INVALID, then

 

 

 

 

(10 to 35)

 

 

 

 

 

 

 

 

 

other means are used to determine the control point. See

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data2.TempControlPt for more information.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DestSptOffset

nviSetPtOffset

 

Degrees F

 

0

 

X

 

X

 

X

X

SetPtOffset is input from an operator terminal or from an energy

 

 

(SNVT_temp_p)

 

-18 to 18

 

 

 

 

 

 

 

 

 

management system used to shift the effective temperature setpoint by

 

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

adding SetPtOffset to the otherwise calculated setpoint. If the value is

 

 

 

 

-10 to 10

 

 

 

 

 

 

 

 

 

outside the allowed range of -10 to +10 degrees C (-18 to 18 degrees F),

 

 

 

 

 

 

 

 

 

 

 

 

 

 

then the node uses the value of the nearest range limit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SrcRmTempActSpt

nvoEffectSetPt

 

Degrees F

 

SI_INVALID

 

X

 

X

 

 

 

EffectSetPt is the current temperature control point (such that the current

 

 

(SNVT_temp_p)

 

50 to 95

 

 

 

 

 

 

 

 

 

actual space temperature setpoint which the controller is presently trying to

 

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

maintain in the conditioned space). See Data2.TempControlPt for more

 

 

 

 

(10 to 35)

 

 

 

 

 

 

 

 

 

details. EffectSetPt is updated according to the SGPU mechanism where a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

significant change is plus or minus 0.07 degrees C (0.13 degrees F).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

74-2958— 1

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER