Honeywell W7750A NviFree1 Value, Auxiliary functions. nviFree1 controls the FREE1OUT, 255 74-2958

Models: W7750A

1 116
Download 116 pages 10.25 Kb
Page 79
Image 79

Table 22. Energy Management Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

DigitalStateor ValueofState

Default

E-Vision(M,P,S)

Share

Map

DirectAccess

HardwareConfig.

ManualConfig.

FailureDetect

Comments

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nviFree1

value

0 to 100

 

0

 

 

 

 

 

 

 

Free1.value network variable controls the spare or Free digital output for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

auxiliary functions. nviFree1 controls the FREE1_OUT,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FREE1_OUT_PULSE_ON, and FREE1_OUT_PULSE_OFF outputs (only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

one of these DO selections per controller is allowed). The states have the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

following meaning: If the state is SW_OFF, the corresponding free logical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output (and therefore the physical output, if configured) is off. If the state is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW_ON and the value is 0, then the corresponding free logical output (and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

therefore the physical output, if configured) is off. If the node receives this

 

 

 

 

 

 

 

 

 

 

 

 

 

 

combination of state and value, then state is set to SW_OFF. If the state is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW_ON and the value is not zero, then the corresponding free logical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

output (and therefore the physical output, if configured) is on. If the state is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW_NUL or other, then the network variable is not bound, the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

communications path from the sending node has failed, or the sending node

 

 

 

 

 

 

 

 

 

 

 

 

 

 

has failed. The corresponding free logical output does not change if the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

network variable input fails.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DestFree1

nviFree1

state

SW_OFF

0

SW_NUL

M

X

 

X

 

X

X

Refer to Free1.value.

 

 

 

 

SW_ON

1

 

 

 

 

 

 

 

 

 

 

 

 

 

SW_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

79

 

nviFree2

value

0 to 100

 

0

 

 

 

 

 

 

 

Free2.value behaves the same as Free 1 value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DestFree2

nviFree2

state

SW_OFF

0

SW_NUL

M

X

 

X

 

X

X

Refer to Free2.value.

 

 

 

 

SW_ON

1

 

 

 

 

 

 

 

 

 

 

 

 

 

SW_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nviWSHPEnable

value

0 to 100

 

0

 

 

 

 

 

 

 

WSHPEnable.value is used to enable the compressor stages in heat pump

 

 

 

 

 

 

 

 

 

 

 

 

 

 

applications. Typically nviWSHPEnable is bound to a water flow sensor that

 

 

 

 

 

 

 

 

 

 

 

 

 

 

detects heating/cooling water supplied to the heat pump. If there is no water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

flowing the compressor is disabled. If the state is SW_OFF, the compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is disabled in heat pump applications. If the state is SW_ON and the value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

is 0, the compressor is disabled in heat pump applications. If the node

 

 

 

 

 

 

 

 

 

 

 

 

 

 

receives this combination of state and value, then state is set to SW_OFF. If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the state is SW_ON and the value is not zero, the compressor is enabled in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heat pump applications. If the state is SW_NUL or other, the network

 

 

 

 

 

 

 

 

 

 

 

 

 

 

variable is not bound and is ignored.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DestWSHPEnable

nviWSHPEnable

state

SW_OFF

0

SW_NUL

 

 

 

 

 

 

X

Refer to WSHPEnable.value.

 

 

 

 

SW_ON

1

 

 

 

 

 

 

 

 

 

 

 

 

 

SW_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 