EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Table 15. Configuration Options Summary For W7750A,B,C Controllers.

 

 

 

 

 

 

 

Possible Configurations for the

 

 

Option

 

W7750A Model

 

Possible Configurations for the W7750B,C Models

 

 

 

 

 

Type of

1.

One stage.

1.

One stage.

Heating

 

 

 

 

2.

Two stages.

2.

Two stages.

 

 

 

 

 

 

3.

Three stages.

3.

Three stages.

 

 

 

 

 

 

4.

Four stages.

4.

Four stages.

 

 

 

 

 

 

5.

None.

5.

Series 60 Modulating electric valve, or pneumatic via transducer.

 

 

 

 

 

 

 

 

6.

Pulse Width Modulating electric valve, or pneumatic via transducer.

 

 

 

 

 

 

 

 

7.

None.

 

 

 

 

 

Type of

1.

One stage.

1.

One stage.

Cooling

 

 

 

 

2.

Two stages.

2.

Two stages.

 

 

 

 

 

 

3.

Three stages.

3.

Three stages.

 

 

 

 

 

 

4.

Four stages.

4.

Four stages.

 

 

 

 

 

 

5.

None.

5.

Series 60 Modulating electric valve, or pneumatic via transducer.

 

 

 

 

 

 

 

 

6.

Pulse Width Modulating electric valve, or pneumatic via transducer.

 

 

 

 

 

 

 

 

7.

None.

 

 

 

 

 

Type of

1.

Digital Output Enable/Disable

1.

Digital Output Enable/Disable signal for controlling an external

Economizer

 

signal for controlling an external

 

economizer package.

 

 

economizer package.

 

 

 

 

 

 

 

 

2.

Series 60 Modulating electric

2.

Series 60 Modulating electric damper motor, or pneumatic via

 

 

damper motor, or pneumatic via

 

transducer.

 

 

transducer.

 

 

 

 

 

 

 

 

3.

None.

3.

Pulse Width Modulating electric damper motor, or pneumatic via

 

 

 

 

transducer.

 

 

 

 

 

 

 

 

4.

None.

 

 

 

 

 

IAQ Option

1.

None.

1.

None.

 

 

 

 

 

 

2.

Local IAQ Digital Input— directly

2.

Local IAQ Digital Input— directly wired to the controller. (Contacts

 

 

wired to the controller. (Contacts

 

closed means poor IAQ is detected.)

 

 

closed means poor IAQ is

 

 

 

 

detected.)

 

 

 

 

 

 

 

 

3.

Network (IAQ Override signal

3.

Network (IAQ Override signal received via the LONWORKS Bus).

 

 

received via the LONWORKS Bus).

 

 

 

 

 

 

 

 

 

4. Local CO2 Analog Input— directly wired to the controller. (The sensor

 

 

 

 

must be a 0 to 10V device representing 0 to 2000 PPM CO2.)

Coil Freeze

1.

None.

1.

None.

Stat Option

 

 

 

 

2.

Local Coil Freeze Stat Digital

2.

Local Coil Freeze Stat Digital Input— directly wired to the controller.

 

Input— directly wired to the controller.

(Contacts closed means that coil freeze condition is sensed.)

 

(Contacts closed means that coil

 

 

 

freeze condition is sensed.)

 

 

 

 

 

 

 

Filter Monitor

1.

None.

1.

None.

Option

 

 

 

 

2.

Local Dirty Filter Digital

2.

Local Dirty Filter Digital Input— directly wired to the controller.

 

 

Input— directly wired to the

 

(Contacts closed means that the filter is dirty.)

 

 

controller. (Contacts closed means

 

 

 

 

that the filter is dirty.)

 

 

 

 

 

 

 

 

 

 

3.

Local Analog Input for Differential Pressure across the Filter (directly

 

 

 

 

wired to the controller). The sensor must be a 2 to 10V device

 

 

 

 

representing 0 to 5 inw (1.25 kPa).

 

 

 

 

 

ROOM TEMPERATURE SENSOR (RmTemp)

This is the room space temperature sensor. This sensor is the T7770 or the T7560A,B Wall Module. When it is configured, it provides the temperature input for the W7750 temperature control loop. If it is not configured, it is required that a room temperature sensor value be transmitted from another

LONWORKS Bus device. If no valid room temperature value is available to the W7750 Controller, the temperature control algorithm in the controller is disabled, causing the heating, cooling, and economizer control outputs to be turned off. If the W7750 Controller is configured for Continuous Fan (rather