Table 21. Control Parameters. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value

Digital

 

E-Vision

 

 

Direct

Hardware

Manual

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

ofState

Stateor

Default

(M, P,S)

Share

Map

Access

Config.

Config.

Test

Comments

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

MaxHtRamp

nciAux1SetPt

ubMaxHtRampS0

Degrees F/Hr

 

 

 

8

P

 

X

X

 

 

 

MaxHtRamp is the maximum heat recovery ramp rate in degrees F

 

 

 

0 to 20

 

 

 

 

 

 

 

 

 

 

 

per hour. This value is used to control the adaptive recovery ramp

 

 

 

Degrees C/Hr

 

 

 

 

 

 

 

 

 

 

 

rate during the HEAT recovery period. The setpoint is changed at a

 

 

 

(0 to 11)

 

 

 

 

 

 

 

 

 

 

 

rate in degrees F per hour depending on the outdoor air temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and the MinHtRamp, OdTempMaxHtRamp, and OaTempMinHtRamp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

parameters. If there is no outdoor air temperature sensor available,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

then ubMinHtRamp is used as the recovery rate.NOTE: Recovery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ramping applies between scheduled heating or cooling setpoint

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

changes from OC_UNOCCUPIED to OC_STANDBY,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OC_UNOCCUPIED to OC_OCCUPIED, and OC_STANDBY to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OC_OCCUPIED. Scheduled setpoint changes from OC_OCCUPIED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to OC_UNOCCUPIED or OC_OCCUPIED to OC_STANDBY do not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

use a ramped setpoint but instead use a step change in setpoint.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Recovery ramps begin before the next scheduled occupancy time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and are ramped from the setpoint for the existing scheduled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

occupancy state to the setpoint for the next occupancy state.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MinHtRamp

nciAux1SetPt

ubMinHtRampS0

Degrees F/Hr

 

 

 

3

P

 

X

X

 

 

 

MinHtRamp is the minimum heat recovery ramp rate in degrees F

 

 

 

0 to 20

 

 

 

 

 

 

 

 

 

 

 

per hour. This value is used to control the adaptive recovery ramp

 

 

 

Degrees C/Hr

 

 

 

 

 

 

 

 

 

 

 

rate during the HEAT recovery period. The setpoint is changed at a

 

 

 

(0 to 11)

 

 

 

 

 

 

 

 

 

 

 

rate in degrees F per hour depending on the outdoor air temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and the MaxHtRamp, OdTempMaxHtRamp, and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OdTempMinHtRamp parameters. If there is no outdoor air

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature sensor available, then MinHtRamp is used as the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

recovery rate. Refer to the NOTE in the comments column for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MaxHtRamp for the conditions that recovery ramping applies to.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OaTempMaxHtRp

nciAux1SetPt

ubOdTempMaxHtRampS0

Degrees F

 

 

 

40

P

 

X

X

 

 

 

OdTempMaxHtRamp is the maximum outdoor air temperature

 

 

 

0 to 100

 

 

 

 

 

 

 

 

 

 

 

parameter that is used to calculate the heat recovery ramp rate

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

 

 

setpoint. This value is used to control the adaptive recovery ramp

 

 

 

(-18 to 38)

 

 

 

 

 

 

 

 

 

 

 

rate during the HEAT recovery period. The setpoint is changed at a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rate in degrees F per hour depending on the outdoor air temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and the MaxHtRamp, MinHtRamp, and OdTempMinHtRamp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

parameters. If there is no outdoor air temperature sensor available,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

then MinHtRamp is used as the recovery rate. Refer to the NOTE in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the comments column for MaxHtRamp for what conditions that

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

recovery ramping applies to.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OaTempMinHtRp

nciAux1SetPt

ubOdTempMinHtRampS0

Degrees F

 

 

 

0

P

 

X

X

 

 

 

OdTempMinHtRamp is the minimum outdoor air temperature

 

 

 

0 to 100

 

 

 

 

 

 

 

 

 

 

 

parameter that is used to calculate the heat recovery ramp rate

 

 

 

Degrees C

 

 

 

 

 

 

 

 

 

 

 

setpoint. This value is used to control the adaptive recovery ramp

 

 

 

(-18 to 38)

 

 

 

 

 

 

 

 

 

 

 

rate during the HEAT recovery period. The setpoint is changed at a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rate in degrees F per hour depending on the outdoor air temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and the MaxHtRamp, MinHtRamp, and OdTempMaxHtRamp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

parameters. If there is no outdoor air temperature sensor available,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

then MinHtRamp is used as the recovery rate. Refer to the NOTE in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the comments column for MaxHtRamp for what conditions that

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

recovery ramping applies to.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OaTempClLkOut

nciAux1SetPt

ubOdClLockOutTempS0

Degrees F

Degrees C

 

 

50

P

 

X

X

 

 

 

When the outdoor air temperature is less than OdClLockOutTemp,

 

 

 

0 to 90

(-18 to 32)

 

 

 

 

 

 

 

 

 

 

the cooling is disabled.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 