Table 23. Status Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value

Digital

 

E-Vision

 

 

Direct

Hardware

Manual

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User Address

NvName

Field Name

(Metric) or States plus Range

ofState

Stateor

Default

(M, P,S)

Share

Map

Access

Config.

Config.

Test

Comments

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

 

 

StatusMode

nvoData1

Mode

START_UP_WAIT

0

 

START_UP_WAIT

 

 

X

 

 

 

 

Mode: The result of the controller determining which mode of operation it

 

(nvoCtlDataG1)

 

HEAT

1

 

 

 

 

 

 

 

 

 

currently is in. At each power-up, the controller remains in the Start-Up and

 

 

 

COOL

2

 

 

 

 

 

 

 

 

 

Wait mode (a random time from 0 to 20 minutes that is based on the units

 

 

 

OFF_MODE

3

 

 

 

 

 

 

 

 

 

network number). After that period, the mode changes to initialize actuators

 

 

 

DISABLED_MODE

4

 

 

 

 

 

 

 

 

 

that will fully close the damper and valve actuators to insure full travel when

 

 

 

EMERG_HEAT

5

 

 

 

 

 

 

 

 

 

under program control. The various other modes are due to normal

 

 

 

SMOKE_EMERGENCY

6

 

 

 

 

 

 

 

 

 

operation as well as manual and network commands.

 

 

 

FREEZE_PROTECT

7

 

 

 

 

 

 

 

 

 

 

 

 

 

MANUAL

8

 

 

 

 

 

 

 

 

 

 

 

 

 

FACTORY_TEST

9

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN_ONLY

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

StatusOcc

nvoData1

EffectOcc

OC_OCCUPIED

0

 

OC_NUL

 

 

X

 

 

 

 

EffectOcc: Result of controller supervising the various Occupied controlling

 

(nvoCtlDataG1)

 

OC_UNOCCUPIED

1

 

 

 

 

 

 

 

 

 

inputs and deciding which one to use. See StatusinOcy, DestSchedOcc,

 

 

 

OC_BYPASS

2

 

 

 

 

 

 

 

 

 

ManualOcc and StatusOvrd.

 

 

 

OC_STANDBY

3

 

 

 

 

 

 

 

 

 

 

 

 

 

OC_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

StatusOvrd

nvoData1

Override

OC_OCCUPIE

0

 

OC_NUL

 

 

X

 

 

 

 

Override: Is the effective manual override state arbitrated from NetManOcc,

 

(nvoCtlDataG1)

 

DOC_UNOCCUPIED

1

 

 

 

 

 

 

 

 

 

the wall module override button and the Bypass Timer.

 

 

 

OC_BYPASS

2

 

 

 

 

 

 

 

 

 

 

 

 

 

OC_STANDBY

3

 

 

 

 

 

 

 

 

 

 

 

 

 

OC_NUL

255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

StatusSched

nvoData1

SchedOcc

OC_OCCUPIED

0

 

OC_NUL

 

 

X

 

 

 

 

DestSchedOcc: DestSchedOcc is calculated from OccTimeClock and

 

(nvoCtlDataG1)

 

OC_UNOCCUPIED

1

 

 

 

 

 

 

 

 

 

nviTodEvent.CurrentState using the following logic: If

 

 

 

OC_BYPASS

2

 

 

 

 

 

 

 

 

 

nviTodEvent.CurrentState is OC_OCCUPIED and OccTimeClock is

 

 

 

OC_STANDBY

3

 

 

 

 

 

 

 

 

 

ST_NUL, then DestSchedOcc is OC_OCCUPIED. If

 

 

 

OC_NUL

255

 

 

 

 

 

 

 

 

nviTodEvent.CurrentState is OC_UNOCCUPIED and OccTimeClock is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ST_NUL, then DestSchedOcc is OC_UNOCCUPIED. If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nviTodEvent.CurrentState is OC_STANDBY and OccTimeClock is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ST_NUL, then DestSchedOcc is OC_STANDBY. If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nviTodEvent.CurrentState is don’t care and OccTimeClock is ST_ON, then

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DestSchedOcc is OC_OCCUPIED. If nviTodEvent.CurrentState is don’t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

care and OccTimeClock is ST_OFF, then DestSchedOcc is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OC_UNOCCUPIED. OC_OCCUPIED means the space is scheduled to be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

occupied. OC_UNOCCUPIED means the space is scheduled to be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unoccupied. OC_STANDBY means the space is scheduled to be in a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

standby state somewhere between OC_OCCUPIED and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OC_UNOCCUPIED.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TimeClckOcc

nvoData1

OccTimeClock

ST_OFF

0

 

ST_NUL

 

 

X

 

 

 

 

OccTimeClock: OccTimeClock shows the state of the physical time clock

 

(nvoCtlDataG1)

 

ST_LOW

1

 

 

 

 

 

 

 

 

 

input via nvoIO.OccTimeClock ORed with nviTimeClk. Valid enumerated

 

 

 

ST_MED

2

 

 

 

 

 

 

 

 

 

values are: ST_OFF means OC_UNOCCUPIED when either the time clock

 

 

 

ST_HIGH

3

 

 

 

 

 

 

 

 

 

input is configured and nvoIO.OccTimeClock is 0 and nviTimeClk is not

 

 

 

ST_ON

4

 

 

 

 

 

 

 

 

 

SW_ON or nviTimeClk.state is SW_OFF and nvoIO.OccTImeClock is not 1.

 

 

 

ST_NUL

255

 

 

 

 

 

 

 

 

ST_ON means OC_OCCUPIED when either the time clock input is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

configured and nvoIO.OccTimeClock is 1 or nviTimeClk.state is SW_ON.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ST_NUL means that the local time clock input is not configured by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

nciIoSelect and nviTimeClk.state is SW_NUL. There is no time clock

 

 

 

 

 

 

 

 

 

 

 

 

 

 

configured or bound to the node.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER