Honeywell W7750A specifications Off

Models: W7750A

1 116
Download 116 pages 10.25 Kb
Page 107
Image 107

 

 

 

 

Table 27. Direct Access And Special Points. (Continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital Stateor Value ofState

 

E

 

 

DirectAccess

 

E-Vision Legend: (M) Monitor, (P) Parameter, (S) Schematic

 

User Address

NvName

Field Name

(Metric) or States plus Range

Default

-Vision (M, P,S)

Share

Map

Test

Comments

 

 

 

 

Engineering Units: English

 

 

 

 

 

 

 

 

 

TestHtClStg1

nviManValue

HeatCoolStage1

OFF

0

OFF

 

 

 

 

X

During MANUAL mode, HeatCoolStage1 parameters turn the corresponding heat,

 

 

 

 

ON

1

 

 

 

 

 

 

or cool stage to on (1) or off (0). When HeatCoolMode is 0, then cooling loads are

 

 

 

 

 

 

 

 

 

 

 

 

controlled. When HeatCoolMode is 1 and the node is controlling conventional

 

 

 

 

 

 

 

 

 

 

 

 

equipment, then heating loads are controlled. When HeatCoolMode is 1 and the

 

 

 

 

 

 

 

 

 

 

 

 

node is controlling a heat pump, then cooling loads are controlled.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TestHtClStg2

nviManValue

HeatCoolStage2

OFF

0

OFF

 

 

 

 

X

For HeatCoolStage2, refer to HeatCoolStage1.

 

 

 

 

ON

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TestHtClStg3

nviManValue

HeatCoolStage3

OFF

0

OFF

 

 

 

 

X

For HeatCoolStage3, refer to HeatCoolStage1.

 

 

 

 

ON

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TestHtClStg4

nviManValue

HeatCoolStage4

OFF

0

OFF

 

 

 

 

X

For HeatCoolStage4. refer to HeatCoolStage1.

 

 

 

 

ON

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TestAuxHt1

nviManValue

AuxHeatCoolStage1

OFF

0

OFF

 

 

 

 

X

AuxHeatCoolStage1—During MANUAL mode when the node is configured to

 

 

 

 

ON

1

 

 

 

 

 

 

control a heat pump and HeatCoolMode is 1, these parameters turn the

 

 

 

 

 

 

 

 

 

 

 

 

corresponding auxiliary heat stage on (1) or off (0).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TestAuxHt2

nviManValue

AuxHeatCoolStage2

OFF

0

OFF

 

 

 

 

X

AuxHeatCoolStage2—During MANUAL mode when the node is configured to

 

 

 

 

ON

1

 

 

 

 

 

 

control a heat pump and HeatCoolMode is 1, these parameters turn the

107

 

 

 

 

 

 

 

 

 

 

 

corresponding auxiliary heat stage on (1) or off (0).

 

 

 

 

 

 

 

 

 

 

 

 

TestAuxHt3

nviManValue

AuxHeatCoolStage3

OFF

0

OFF

 

 

 

 

X

AuxHeatCoolStage3—During MANUAL mode when the node is configured to

 

 

 

 

ON

1

 

 

 

 

 

 

control a heat pump and HeatCoolMode is 1, these parameters turn the

 

 

 

 

 

 

 

 

 

 

 

 

corresponding auxiliary heat stage on (1) or off (0).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TestAuxHt4

nviManValue

AuxHeatCoolStage4

OFF

0

OFF

 

 

 

 

X

AuxHeatCoolStage4—During MANUAL mode when the node is configured to

 

 

 

 

ON

1

 

 

 

 

 

 

control a heat pump and HeatCoolMode is 1, these parameters turn the

 

 

 

 

 

 

 

 

 

 

 

 

corresponding auxiliary heat stage on (1) or off (0).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TestHtClMode

nviManValue

HeatCoolMode

OFF

0

OFF

 

 

 

 

X

During MANUAL mode, HeatCoolMode determines whether heating or cooling

 

 

 

 

ON

1

 

 

 

 

 

 

outputs are turned on or off manually. When HeatCoolMode is 0, then cooling loads

 

 

 

 

 

 

 

 

 

 

 

 

are controlled. When HeatCoolMode is 1 and the node is controlling conventional

 

 

 

 

 

 

 

 

 

 

 

 

equipment, then heating loads are controlled. When HeatCoolMode is 1 and the

 

 

 

 

 

 

 

 

 

 

 

 

node is controlling a heat pump, then cooling loads are controlled by Heat / Cool

 

 

 

 

 

 

 

 

 

 

 

 

stages and heating stages are controlled by auxiliary heat stages. The

 

 

 

 

 

 

 

 

 

 

 

 

CHANGE_OVER_RELAY_OUT is affected by HeatCoolMode as configured in

 

 

 

 

 

 

 

 

 

 

 

 

Select.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TestSaFan

nviManValue

FanOut

OFF

0

OFF

 

 

 

 

X

During MANUAL mode, FanOut turns the fan on (1) or off (0).

 

 

 

 

ON

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TestAuxEcon

nviManValue

AuxEconOut

OFF

0

OFF

 

 

 

 

X

During MANUAL mode, AuxEconOut turns the AUX_ECON_OUT on(1) or off(0).

 

 

 

 

ON

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TestOccStat

nviManValue

OccStatusOut

OFF

0

OFF

 

 

 

 

X

During MANUAL mode, OccStatusOut turns the OCCUPANCY_STATUS_OUT to

 

 

 

 

ON

1

 

 

 

 

 

 

on(1 = not OC_UNOCCUPIED) or off (0).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TestFree1

nviManValue

Free1Out

OFF

0

OFF

 

 

 

 

X

During MANUAL mode, Free1Out turns the FREE1_OUT on(1) or off(0).

 

 

 

 

ON

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TestFree2

nviManValue

Free2Out

OFF

0

OFF

 

 

 

 

X

During MANUAL mode, Free2Out turns the FREE2_OUT on(1) or off(0).

74-2958— 1

 

 

 

ON

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

Page 107
Image 107
Honeywell W7750A specifications Off