Honeywell W7750A Terminal Terminal Number Description, Factory Default Digital Outputs

Models: W7750A

1 116
Download 116 pages 10.25 Kb
Page 37
Image 37

 

 

EXCEL 10 W7750A,B,C CONSTANT VOLUME AHU CONTROLLER

 

 

Table 10. W7750A Version I/O Description.

 

 

 

Terminal

Terminal Number

Description

 

 

 

DO6–(W1)

31

Heat 1 (or Reversing Valve for a Heat Pump)

 

 

 

DO5–(W2)

30

Heat 2 (or Aux. Heat for a Heat Pump)

 

 

 

DO4–(Y1)

29

Cool 1 (or Compressor 1 for a Heat Pump)

 

 

 

DO3–(Y2)

28

Cool 2 (or Compressor 2 for a Heat Pump)

 

 

 

DO2–(G)

27

Fan

 

 

 

DO1–NET

26

Network Digital Output

 

 

 

DO1–NET

25

Network Digital Output (connect to terminal number 22 +24Vac)

 

 

 

Rc

24

Control power for relay contacts DO2 (G), DO3 (Y1) and DO4 (Y2)

 

 

 

Rh

23

Control power for relay contacts DO5 (W1) and DO6 (W2)

 

 

 

+24Vac (H)

22

Power for the controller

 

 

 

COM (N)

21

Return for power to controller

 

 

 

E-Bus

14 and 15

Echelon communications (LONWORKS Bus) screw terminals

 

 

 

DI - 2

12

Digital Input 2

 

 

 

DGND

11

Digital Ground

 

 

 

DGND

10

Digital Ground

 

 

 

DI - 1

9

Digital Input 1

 

 

 

AGND

8

Analog ground

 

 

 

AI - 1 OHM

7

Analog Input 1 (used for Discharge Air Temperature Sensor)

 

 

 

SET PT

6

Space temperature setpoint potentiometer

 

 

 

GROUND

5

Wall Module

 

 

 

SENSOR

4

Space temperature sensor

 

 

 

BYPASS

3

Space override button

 

 

 

LED

2

Space LED for indication of manual occupancy status

 

 

 

EARTH GND

1

Earth Ground

 

 

 

IMPORTANT

If the W7750A controller is configured by E-Vision, the outputs may be assigned in different order than the factory defaults. Use the Custom Wiring function of E-Vision to re-assign the outputs to the desired terminals.

The W7750B,C Versions are preconfigured with the same factory default setup as the W7750A Model; however, some terminals for wiring connections differ on the W7750B,C Models. See Fig. 30 for the terminal names on the W7750B Model and Fig. 35 for the terminal names on the W7750C Model. The factory default configuration of the digital output points on the W7750B,C Models follow (terminal names are from the W7750A):

FACTORY DEFAULT DIGITAL OUTPUTS:

FREE 1 (OUT 1) DO1— NETWORK DO (OUT 2) DO2— SUPPLY FAN START/STOP

(OUT 3) DO3— COOL_STAGE_2

(OUT 4) DO4— COOL_STAGE_1

(OUT 5) DO5— HEAT_STAGE_2

(OUT 6) DO6— HEAT_STAGE_1 DO7— UNUSED

DO8— UNUSED

The Wall Module terminals are identical for the W7750A,B,C Models.

The W7750B,C Models offers two voltage/current sensor input terminals. When current-type sensors (4 to 20 mA) are configured, the W7750B,C automatically switches a 249 ohm resistor into the sensing circuit; so no external resistor is required. The W7750A Model does not support voltage or current inputs.

NOTE: If using factory defaults, DI-2 input is configured for ScheduleMaster (nvoIO.SchedMaster). For a stand-alone unit, either connect an external time clock to terminals 9 and 10 or put a jumper on terminals 9 and 10 (using a jumper puts the controller in continuous occupied mode).

37

74-2958— 1